20 Supplemental Installation Manual for ACS580-0P
ACS580-0P
ACH580-PxR-052A-6
3
52 50 R5 Class T 80A N/A N/A
ACH580-PxR-062A-6 62 60 R5 Class T 80A N/A N/A
ACH580-PxR-077A-6 77 75 R5 Class T 100A N/A N/A
ACH580-PxR-099A-6 99 100 R7 Class T 150A N/A N/A
ACH580-PxR-125A-6 125 125 R7 Class T 175A N/A N/A
ACH580-PxR-144A-6 144 150 R8 Class T 200A N/A N/A
ACH580-PxR-180A-4 180 150 R2 Class T 300A N/A N/A
ACH580-PxR-240A-4 240 200 R2 Class T 350A Class J
or RK1
400A Max
1)
“0P” represents a disconnect and 0P+F255 represents a circuit breaker.
2) ACS580-0P-xxxx-x+F255 is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye
source only.
3) ACS580-0P-xxxx-x+F255 supports Delta network configuration.
575 Volt
Nominal Output
Range
Base
Drive
Frame
Size
Internal Drive
Fuse Rating
External Fuse for
Disconnect Option
Type Code
1, 2
Drive
Current
Package
Power
A HP Class
Current
Rating
Class
Max Current
Rating