Maintenance
109
Maintenance
What this chapter contains
This chapter contains preventive maintenance instructions.
Safety instructions
Only a qualified electrician is allowed to perform the maintenance.
Before starting work inside the cabinet,
isolate the drive from the supply (note that any switch-disconnector installed in
the drive does not switch off the voltage from the input terminals)
wait for 5 minutes to let the intermediate circuit capacitors discharge
open the cabinet doors
ensure there is no dangerous voltage present by measuring the voltage of the
input terminals and the intermediate circuit terminals.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Interval Maintenance action Instruction
Every year of storage Capacitor reforming
See document ACS 600/800 Capacitor Reforming
Guide (Code: 3BFE 64059629 [English]) and
Capacitors.
Every 6 to 12 months (depending
on dustiness of environment)
Heatsink temperature
check and cleaning
See Heatsinks.
Every year (IP22 and IP42 units)
Air filter check;
replacement if necessary
See Checking and replacing the air filters.
Every year (IP54 units) Air filter replacement
Every 3 years (Frame R8i and
larger units)
Quick connector check
and cleaning
See Quick connectors (Frame R8i and up).
Every 6 years
Cabinet cooling fan
change
See Cooling fans.
Power module cooling fan
change
See Cooling fans.
Every 10 years Capacitor change See Capacitors.