ABB ACS880-14 - Terminal and Entry Data for the Power Cables

ABB ACS880-14
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
US
2)
IEC
1)
Al cable typeCu cable typeAl cable typeCu cable typeACS880-
14-…
AWG/kcmilAWG/kcmilmm
2
mm
2
U
n
= 500 V
250 MCM or 2 × 13/02 × (3 × 70)1 × (3 × 120)240A-5
350 MCM or 2 × 2/0250 MCM or 2 × 13 × (3 × 70)2 × (3 × 50)260A-5
500 MCM or 2 × 3/0300 MCM or 2 × 1/03 × (3 × 70)2 × (3 × 70)302A-5
500 MCM or 2 × 3/0350 MCM or 2 × 2/03 × (3 × 70)2 × (3 × 120)361A-5
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 50)414A-5
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)460A-5
2 × 400 MCM or 3 × 4/02 × 250 MCM or 3 × 2/03 × (3 × 120)3 × (3 × 95)503A-5
U
n
= 690 V
3/01/02 × (3 × 50)1 × (3 × 70)142A-7
4/02/02 × (3 × 50)2 × (3 × 50)174A-7
300 MCM or 2 × 1/04/02 × (3 × 70)2 × (3 × 50)210A-7
400 MCM or 2 × 2/0300 MCM or 2 × 1/03 × (3 × 50)2 × (3 × 70)271A-7
600 MCM or 2 × 4/0 or 3 × 1/0400 MCM or 2 × 2/02 × (3 × 120)2 × (3 × 50)330A-7
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 70)370A-7
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/02 × (3 × 185)3 × (3 × 70)430A-7
1)
The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
2)
The cable selection is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.
Terminal and entry data for the power cables
4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM)Maximum accepted
cable size
M12Screw size for connect-
ing busbars to the drive
module input and output
busbars
50…75 N·m (37…55 lbf·ft)Tightening torque
Protection classes for module
IP20 (standard)Degrees of protection
(IEC/EN 60529)
IP00 (option +0B051)
UL Open TypeEnclosure types (UL
50/50E)
IIIOvervoltage category
(IEC/EN 60664-1)
IProtective class
(IEC/EN 61800-5-1)
282 Technical data and references