10   Introduction to the manual
In addition to this manual, 
• for ACS880 single drives, see the drive hardware manual
• for ACS880 air-cooled multidrives, see Safety instructions for ACS880 multidrive 
cabinets and modules (3AUA0000102301 [English]).
The function described in this manual activates the Safe torque off (STO) function of the 
drive/inverter unit. The STO function of the ACS880 drives is certified (SIL 3 according to 
EN/IEC 61800-5-2 and IEC 61508). For a detailed description of the STO function, see the 
hardware manual of your drive/inverter unit.
WARNING! The functions described in this manual do not disconnect the voltage 
of the main and auxiliary circuits from the drive. Never work on the electrical parts 
of the drive or the motor before you have also disconnected the drive system from 
the electric supply, from rotating permanent magnet motors and from rotating motors 
equipped with sine filters, and made sure by measuring that there is no dangerous voltage 
present.
WARNING! The STO function of ACS880 drives cannot prevent the intermediate 
DC current from flowing through, and heating up, the motor in case a short-circuit 
occurs in the output stage of the drive. The supplier must take this into account 
when planning the protection of the installation.
Note: When you connect the temperature sensor(s) of the Ex motor to the drive STO 
terminals through a relay, ensure the availability of required reinforced (double) insulation 
between the main circuit (motor) and the control unit. For example, the insulation of the 
temperature sensor in the Ex motor and the insulation of the protection relay affect the 
insulation of the whole circuit. All Ex motors manufactured by ABB have basic insulation 
between the main circuit and the temperature sensor. Similarly, ABB protection relays 
have basic insulation between the sensor circuit and relay output. This ensures double 
insulation for the ATEX-certified motor thermal protection function between the main circuit 
and the drive control unit.
 Example circuit diagrams of this manual
The purpose of the example circuit diagrams is to help in understanding the operation of 
the ATEX-certified motor thermal protection functions. The diagrams do not cover all 
possible details and variants of the drives. The component designations do not necessarily 
match each drive. 
WARNING! Never connect, test or measure a drive based on the diagrams of this 
manual. Each delivery is unique. Before you start the work on the electric circuits 
of a drive, always refer to the delivery-specific circuit diagrams.