EasyManua.ls Logo

ABB ANSI - Page 27

ABB ANSI
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COMMISSIONING AND TESTING GUIDE 27
Step 2/7
Warning: Ensure that all equipment is de-
energized and all safety interlocks and/or lock-
out-tag-out procedures are followed to ensure
equipment is safe to work on in primary
compartments.
Step 3/7
Isolate tested phases. Remove the circuit
breaker out of the switchgear frame. Any high
voltage cables terminated at the frame should
be disconnected for safety reasons.
Step 4/7
Except the tested phase, connect all other
phases together to the grounding bar.
Step 5/7
Connect the primary tester to the cable
connection end of the isolated phase and to the
ground bus inside the switchgear frame. (Note:
ground bus connection can be made in breaker
or cable compartment.)
Since the protection relay is reporting phase-to-
phase voltages, two identical measurements will
appear on the display. For example, if voltage is
applied between phase 1 and the ground, then

Voltage sensor installed on main bus
Step 1/8
Verify sensor parameters set in the protection
relay with sensor rating plates found on the
sensors. These may be found on the circuit
breaker compartment door or in the low voltage
wiring compartment.
WARNING
42 Test setup for voltage
sensors installed in the
cable compartment
43 Measurements
view, injected phase 1
44 Example of a
voltage sensor label
45 Voltage sensor
parameters
43
42
45
44
On the protection relay LHMI go to -> Main Menu/
Configuration/Analog inputs/Voltage (3U, VT)
Primary voltage = Nominal voltage of the
network
VT connection = Wye (star connection)
Amplitude Corr A = sensor rating plate, phase A
Amplitude Corr B = sensor rating plate, phase B
Amplitude Corr C = sensor rating plate, phase C
Division ration = 10 000
Voltage input type = RVD sensor
Angle Corr A = sensor rating plate phase A
Angle Corr B = sensor rating plate phase B
Angle Corr C = sensor rating plate, phase C
L1
L2
L3
No
circuit
breaker
U
0V 0V
Primary
tester
~U (V)

Related product manuals