WARNING!
Electric shock due to wrongdoing during hot swapping!
To avoid electric shock
follow these conditions for hot swapping:
Digital outputs are not under load.
Input/output voltages above safety extra low voltage/
protective extra low voltages (SELV/PELV) are switched off.
Modules are completely plugged on the terminal unit with both snap fit
engaged before switching on loads or input/output voltage.
Never touch exposed contacts (dangerous voltages).
Stay away from electrical contacts to avoid a skipping arc.
Do not operate improperly mechanical installation.
H = Hot swap
Hot swap
System requirements for hot swapping of I/O modules:
Hot-swappable terminal units have the appendix TU5xx-H.
I/O modules as of index F0.
Communication interface modules CI5xx as of index F0.
The index of the module is in the right corner of the label.
NOTICE!
Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from
the terminal unit in a powered system.
DO524
2019/11/153ADR024117M02xx, 11, en_US172