…5.2 Operating Page Displays
Profile Program Selected
Profile Status:
StOP – waiting for run command, profile is inactive
rAMP – program is running and ramping
SOAK – program is running and soaking
HOLd – operator hold or controller is in manual
H–HOLd – holdback hold in hold, due to guaranteed ramp/
soak hysteresis values being exceeded
r–HOLd – retort function has placed controller in hold
r–rAMP – retort function is ramping set point back to soak
value
END – current program is completed but digital input
signal is in 'Run' state.
Current Profile Segment
Time Remaining
Time remaining until the end of the current segment (in minutes or hours),
depending on the
Ramp/Soak Time Units set in the Profile Control Page,
Advanced Software Options Manual. 'h' is displayed if hours are selected.
Use the
or switches to add or subtract the extended time from the
soak time. Refer to the
Profile Control Page. If the extended soak value is
set to '0' the
Time Remaining feature is disabled.
Repeat Count
Remaining number of times the current profile is to be repeated.
Current Time
Time (displayed using 24hr clock)
Current Date
Day and Month
Timer Option
bIAS
0.0
100.3
110.5
PrG 1
rAMP
SEG 12
t–– h
rPt-Ct
3
tIME
12:00
dAtE
24 JAN
No
Timer Option
100.3
110.5
StOP
rAMP
SOAK
HOLd
H–HOLd
r–HOLd
r–rA–P
ENd
Profile Option
bIAS
0.0
E––h
Alternates
between the two
displays when
extended soak
is selected.
E––h
displays
amount of time
soak extended
by.
5 CONTROL OPERATION…