L2234
L2778
Emax
22/158
Doc. No.
Model
Apparatus
Scale
Page No.
1SDH000460R0002
Fig. 33b
8.3.4 Operating mechanism maintenance
Carry out the checks and take the action listed under item 1 of the table in paragraph 8.3.2.
Lubricate the bearings of the drive shaft with MU-EP1 (AGIP) grease, including those on the sides of the circuit-breaker. Equivalent greases:
ESSO Beacon EP1 - BP LTX1 - SHELL AVANIA GREASE R1 - KLUBER LUBRIFICATION CENTO PLEX 2P
Lubricate the small opening and closing shafts and the hooks with 5 RX MOLY (OLEOTECNICA) grease (Fig. 33c). Equivalent grease: KLUBER
LUBRIFICATION GRAFLOSCON A-G 1 ULTRA.
Fig. 33a
Fig. 33c