L2234
Emax
87/158
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000460R0002
L2778
(1)
The minimum value of this trip is 1s regardless of the type of curve set (self-
protection).
(2)
These tolerances are based on the following assumptions:
- self-supplied relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
- preset trip time 100 ms
(3)
no-trip time
(4)
the protection G is disabled for current values greater than 4In, where I4 < 0.5 In,
greater than 6 In, where 0.5 In I4 < 0.8 In and greater than 8 In where I40.8 In.
(5)
Max trip time
For all cases not covered by the above hypotheses, the following tolerance values
apply:
Protections Trip threshold Trip time
L Release between 1.05 and 1.25 x I1 ± 20%
S ± 10% ± 20%
I ± 15% 60ms
G ± 10% ± 20%
Others ± 20%
LC1/LC2 loads  50%÷100% step 0.05xI
1
control
Warning Iw  0,3÷10I
n
step 0,05xI
n
± 10% 10÷40 ms
Protection
Threshold
range
Time
Tolerance
(2)
Time
range
Threshold
tolerance
(2)
Disabling
Disabling
TRIP only
Zone
selectivity
Start-up threshold
Thermal memory
14.2.9.16 Table of measurements
Type of measurement Standard operation range
Range of values measured by the relay Range Tolerance %
Phase and neutral currents 0,05 ... 16 In 0,3 ... 6 In ± 1,5
Internal ground fault current 0,05 ... 4 In 0,3 ... 4 In ± 1,5
(internal source round return)
External ground fault current 0,05 ... 4 In 0,3 ... 4 In ± 1,5
(external source round return)
Phase-to-phase and phase voltages 10 V
conc
... 1,1x690 V
conc
50 V
conc
... 1,1x690 V
conc
± 1
(measured at the module's input
and thus independent of the precision
relating to the use of any VT)
Residual voltage 10 V
conc
... 1,1x690 V
conc
50 V
conc
... 1,1x690 V
conc
± 1
(for systems with neutral only)
Peak factor 0,1 ... 6 In 0,3 ... 6 In ± 1,5
Total power factor 0,1 ... 1 0,5 ... 1 ± 2,5
Mains frequency 35 ... 80 Hz 45 ... 66 Hz ± 0,2
Instantaneous active power on the 0,02 ... 16 Pn 0,3 ... 6 Pn ± 2,5
single phase and total system
Instantaneous reactive power on the 0,02 ... 16 Pn 0,3 ... 6Pn ± 2,5
single phase and total system
Instantaneous apparent power on 0,02 ... 16 Pn 0,3 ... 6Pn ± 2,5
the single phase and total system
Active energy 0,02 ... 16 Pn 0,3 ... 6Pn ± 2,5
Reactive energy 0,02 ... 16 Pn 0,3 ... 6 Pn ± 2,5
Apparent energy 0,02 ... 16 Pn 0,3 ... 6 Pn ± 2.5