3. Switching from “earthed” position to “open” position
a) Fit operating lever into lower hole.
b) Turn lever clockwise to “earthed” position.
4. Switch-disconnector opening from “earthed” position
a) Close cable compartment door.
b) “Earthed” position
Fig. 43 - “Earthed” position
Fig. 44 - “Earthed” position
Fig. 45 - “Earthed” position with operating lever in lower hole
Fig. 42 - “Open” position with operating lever in lower hole.
Fig. 46 - “Open” position
NOTE
The cable compartment door can only be
opened when the switch-disconnector is in
the “earthed” position.
c) Fit operating lever into lower hole.
d) Turn lever counter-clockwise to “open” position.