Operation Manual / A150-M56/66/57/67 - A155-M..
10 Dismantling and fitting with removed air inlet and gas outlet / 10.5
Removing the compressor casing
© Copyright 2021 ABB. All rights reserved. HZTL4032_EN Rev.Q January 2021
Dismantling the diffuser and the wall insert
Fig.58: Dismantling the diffuser and the wall insert
1. Loosen the screws (79041) and remove with fixing discs (79040).
2. Remove diffuser (79000).
3. Fit the swivel lifting eye (S) to the wall insert (77000). Secure lifting gear to the swivel lift-
ing eye.
4. Remove the wall insert (77000). When doing this, make sure that the wall insert does not
"stick" to the compressor casing (72000).
5. Remove and dispose of the O-ring (77005).