EasyManua.ls Logo

ABB ICMK14F1

ABB ICMK14F1
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming 5 – 10 Advant Controller AC 31 / Issued: 01.99
3
Initialization: word flags
Õ Absolute identifier: KW 00,02
Õ Symbolic identifier: INIT_MW
Value n of the system constant KW 00,02
Word flag areas which are initialized (set
to 0)
n = 0 (default) MW 000,00...MW 099,15
MW 230,00...MW 255,15
n = 1...99 MW n,00...MW 099,15
MW 230,00...MW 255,15
n = 100...229 MW 230,00...MW 255,15
n = 230...255 MW n,00...MW 255,15
n < 0, n > 255 No initialization
Initialization: double word flags
Õ Absolute identifier: KW 00,03
Õ Symbolic identifier: INIT_MD
Value n of the system constant KW 00,03
Double word flag areas which are
initialized (set to 0)
n = 0 (default) MD 000,00...MD 001,15
n = 1 MD 001,00...MD.001,15
n < 0, n > 1 No initialization
Initialization: step chains
Õ Absolute identifier: KW 00,04
Õ Symbolic identifier: INIT_S
Value n of the system constant KW 00,04
Step chains which are initialized (set
to 0)
n = 0 (default) S 000,00...S 125,15
n = 1...125 S n,00...S 125,15
n < 0, n > 125 No initialization
Initialization: historical values
Õ Absolute identifier: KW 00.05
Õ Symbolic identifier: INIT_VW
Value n of the system constant KW 00,05
Historical values which are initialized (set
to 0)
n = 0 (Default) Initialization of all historical values
n < 0,n > 0 No Initialization

Table of Contents

Related product manuals