EasyManua.ls Logo

ABB M4M 30 - Page 11

ABB M4M 30
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M4M 30 NETWORK ANALYZER USER MANUAL
11
I/O
Digital Output
Voltage (min - max) 5 - 240 VAC/DC
Current (min - max) 2 - 100 mA
Max ON state drop voltage 1,5 V
Max R value at Min voltage conditions (5 V) 1750 Ohm
Min R value at Max voltage conditions (240 V) 2400 Ohm
Pulse duration [ms] 20 ms ON, 20 ms OFF
Pulse frequency 25 Hz
Alarm activation delay [s] 1 - 900 s (programmable)
Alarm return hysteresis 0 - 40% (programmable)
Digital Input
Maximum Voltage 240 VAC/DC
Max voltage for OFF state on input 20 VAC/DC
Min voltage for ON state on input 45 VAC/DC
Analogue Output
Programmable electrical parameters Span [0 - 20 mA or 4 - 20 mA]
Load Typical 250 Ohm, max 500 Ohm
Mechanical characteristics
Overall dimensions
96 mm x 96 mm x 77,5 mm
(Depth inside the switchboard: 57mm )
IP degree of protection (IEC 60529) Front: IP54
Terminals: IP20
Weight [g] 400
Terminal characteristics
Voltage inputs
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 7,62 mm
Poles: 4
Current inputs
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 8
Screw flanges for fixing
RS-485 Serial port
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 3
I/O
Nominal cross section: 2,5
mm
2
Solid/stranded wire: 0,2 - 2,5
mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 5 (Programmable I/O)
Poles: 3 (Programmable I/O only on M4M 30
I/O)
Poles: 3 (Analogue outputs, only on M4M 30 I/O)
Rogowski current probes
Only with ABB Rogowski probes:
-
R4M-200: 200 mm diameter (2CSG202150R1101)
-R4M-80: 80 mm diameter (2CSG202160R1101)