Installation
Wiring
Use 0.5 to 1.5 mm
2
(20 to 16 AWG) cable with an appropriate
voltage rating for digital signals.
Refer to “Terminal Designations” on page 9 and connect control
wires to the MREL-01 module.
Terminal Designations
Use the following table for reference when wiring terminals.
Apply Power
1. Turn on the mains power to the drive.
2. Continue to the next section, Start-Up.
Identification Hardware Description
1 COM OUTPUT RELAYS K2-K4:
Max. continuous current:
2 A rms (cos ϕ = 1),
1 A rms (cos ϕ = 0.4)
Max. switching capability:
6 A (24 V DC, resistive load)
1500 VA (250 V AC)
Galvanically isolated from each other (2.5 kV AC,
1 min.)
2NC
3NO
1COM
2NC
3NO
1COM
2NC
3NO
K2
K3
K4