Emax X1-Tmax T7-Tmax T8
Operating istructions for T7-T8-X1 low
voltage air circuit breakers protection
releases
Operating instructions
1SDH000587R0002
B1751

Table of Contents

Questions and Answers

  • N
    Nathan EdwardsAug 9, 2025
    Why are the ABB Tmax T8 trip times higher than expected?
    • C
      Christina PopeAug 9, 2025
      If the trip times for your ABB Other are higher than expected, the threshold or curve might be set too high. Another possibility is that the curve type is set to "t=k/I2". Finally, the neutral selection could be incorrect. To resolve this, correct the threshold and curve, select the curve type "t=k", and ensure the neutral adjustment is correct.
  • M
    Miss Denise TaylorAug 14, 2025
    Why are the ABB Other trip times lower than expected?
    • A
      adammanningAug 14, 2025
      If the trip times for your ABB Other are lower than expected, it could be due to a threshold or curve that is set too low, or an incorrect neutral selection. To fix this, correct the threshold and curve settings, and ensure the neutral adjustment is correct.
  • M
    melissawilsonAug 20, 2025
    How to troubleshoot ABB Other when the trip test cannot be run?
    • A
      Amanda SmithAug 20, 2025
      If the trip test for your ABB Other cannot be run, it could be due to several reasons. First, check if the busbar current is greater than 0, as it should be in normal operation (FN). Second, verify the TC connection. Lastly, ensure the PR030/B unit is properly connected.
  • A
    Alexis FowlerAug 27, 2025
    What to do if the expected trip does not happen with ABB Other?
    • A
      Allison PerezAug 27, 2025
      If the expected trip does not occur with your ABB Other, the protection function might be turned off. To resolve this, enable the protection function (FN).
  • M
    Madeline TownsendSep 2, 2025
    What causes rapid trip with I3=Off in ABB Tmax T8?
    • E
      Erica ShawSep 2, 2025
      A rapid trip with I3=Off in your ABB Other is likely caused by an instantaneous trip (Iinst tripped). This suggests a short-circuit with high current (FN).

Summary

Protection Release General Notes

Safety and Warning Notes

Provides crucial safety information and warnings for handling the product.

Protection Release PR331;P

PR331;P Protection Functions

Describes various protection functions (L, S, I, G) and their parameters.

PR331;P Installation and Setup

Provides instructions for installation, connections, and initial setup procedures.

PR331;P Troubleshooting

Offers guidance for diagnosing and resolving common faults and malfunctions.

Protection Releases PR332;P and PR333;P

PR332;P and PR333;P User Menus

Describes how to navigate and utilize the device's menu structure for configuration.

PR332;P and PR333;P Protection Functions

Details various protection functions (L, S, S2, D, G, U, etc.) and their parameters.

PR332;P and PR333;P Settings Menu

Outlines available settings for circuit breaker, frequency, modules, and system configuration.

PR332;P and PR333;P Test Menu

Describes the options available for testing the protection release and circuit breaker.

ABB Tmax T8 Specifications

General IconGeneral
ModelTmax T8
Poles3, 4
Rated Impulse Withstand Voltage (Uimp)12 kV
Breaking Capacity100 kA at 415 V AC
StandardsIEC 60947-2
Rated Current (In)800 A
Rated Voltage (Ue)690 V
Rated Insulation Voltage (Ui)1000 V
TypeCircuit Breaker
Rated current800 A
Trip unitElectronic