Why are the ABB Tmax T7 trip times higher than expected?
J
jgrahamJul 27, 2025
If the trip times for your ABB Other are higher than expected, the threshold or curve might be set too high. Another possibility is that the curve type is set to "t=k/I2". Finally, the neutral selection could be incorrect. To resolve this, correct the threshold and curve, select the curve type "t=k", and ensure the neutral adjustment is correct.
J
Jennifer SuttonAug 2, 2025
Why are the ABB Tmax T7 trip times lower than expected?
B
Benjamin PerezAug 2, 2025
If the trip times for your ABB Other are lower than expected, it could be due to a threshold or curve that is set too low, or an incorrect neutral selection. To fix this, correct the threshold and curve settings, and ensure the neutral adjustment is correct.
M
Megan SanchezAug 8, 2025
How to troubleshoot ABB Tmax T7 when the trip test cannot be run?
C
Cody ShepherdAug 8, 2025
If the trip test for your ABB Other cannot be run, it could be due to several reasons. First, check if the busbar current is greater than 0, as it should be in normal operation (FN). Second, verify the TC connection. Lastly, ensure the PR030/B unit is properly connected.
F
fwhiteAug 14, 2025
What to do if the expected trip does not happen with ABB Tmax T7?
P
pattonbenjaminAug 14, 2025
If the expected trip does not occur with your ABB Other, the protection function might be turned off. To resolve this, enable the protection function (FN).
W
William MartinezAug 20, 2025
What causes rapid trip with I3=Off in ABB Other?
K
Keith HernandezAug 20, 2025
A rapid trip with I3=Off in your ABB Other is likely caused by an instantaneous trip (Iinst tripped). This suggests a short-circuit with high current (FN).