2 Model Definition
PCS100 ESS User Manual | 2UCD190000E001 rev. J 12
2.3 PCS100 ESS Model Range
The model ratings of the PCS100 ESS are defined by the number of power modules used to construct the system. The
PCS100 ESS product range is summarized in section 2.3.1 for D-type modules and in section 2.3.2 for C-type modules.
The ratings are given for a typical PCS100 ESS system under nominal conditions.
Note: Operation at different voltages than nominal will affect the power rating. Consult 2UCD190000E025 PCS100 ESS
Detailed Sizing Tool for the exact rating according to your operating conditions.
PCS100 ESS D-Type Model Range
Number of Mod-
ules
Dimensions
H x W x D (mm)
Weight
kg
Rated Current
Iac (A)
Heat dissipation
kW (Typical)
Airflow
(m
3
/min)
Type Code
1 2154x809x804
790
150
4.9
1
14 PCS100 19-01D-A10+T000
2
2 2154x809x804 920 300 8.8
1
24 PCS100 19-02D-A10+T000
2
1 2154x809x804 330 150 2.9 10 PCS100 19-01D-A10
2 2154x809x804
410
300
5.8
20 PCS100 19-02D-A10
3 2154x809x804
490
450
8.7
30 PCS100 19-03D-A10
4 2154x809x804
570
600
11.6
40 PCS100 19-04D-A10
5 2154x809x804
650
750 14.4 50 PCS100 19-05D-A10
6 2154x809x804
730
900 17.3 60 PCS100 19-06D-A10
4 2200x1041x703
560
600 11.5 40 PCS100 19-04D-B1x
3
5 2200x1041x703 630 750 14.4 50 PCS100 19-05D-B1x
3
6 2200x1041x703 700 900 17.3 60 PCS100 19-06D-B1x
3
7 2200x1041x703
770
1050 20.1 70 PCS100 19-07D-B1x
3
8 2200x1041x703
840
1200 23.0 80 PCS100 19-08D-B1x
3
9 2200x2041x703
1020
1350 25.9 90 PCS100 19-09D-B2x
3
10 2200x2041x703
1080
1500 28.8 100 PCS100 19-10D-B2x
3
11 2200x2041x703
1150
1650 31.6 110 PCS100 19-11D-B2x
3
12 2200x2041x703
1220
1800 34.5 120 PCS100 19-12D-B2x
3
13 2200x2041x703 1300 1950 37.4 130 PCS100 19-13D-B2x
3
14 2200x2041x703 1370 2100 40.3 140 PCS100 19-14D-B2x
3
15 2200x(1041+2041)x703
1710
2250 43.1 150 PCS100 19-15D-C
5
2x
3
16 2200x(1041+2041)x703
1780
2400 46.0 160 PCS100 19-16D-C
5
2x
3
17 2200x(1041+2041)x703
1850
2550 48.9 170 PCS100 19-17D-B3x
4
18 2200x(1041+2041)x703
1920
2700 51.8 180 PCS100 19-18D-B3x
4
19 2200x(1041+2041)x703
1990
2850 54.6 190 PCS100 19-19D-B3x
4
20 2200x(1041+2041)x703
2070
3000 57.5 200 PCS100 19-20D-B3x
4
21 2200x(1041+2041)x703 2140 3150 60.4 210 PCS100 19-21D-B3x
4
22 2200x(1041+2041)x703 2210 3300 63.3 220 PCS100 19-22D-B3x
4
23 2200x(2041+2041)x703
2280
3450 66.1 230 PCS100 19-23D-C
5
3x
4
24 2200x(2041+2041)x703
2350
3600 69.0 240 PCS100 19-24D-C
5
3x
4
25 2200x(2041+2041)x703
2520
3750 71.9 250 PCS100 19-25D-B4C
26 2200x(2041+2041)x703
2590
3900 74.8 260 PCS100 19-26D-B4C
27 2200x(2041+2041)x703
2660
4050 77.6 270 PCS100 19-27D-B4C
28 2200x(2041+2041)x703
2730
4200 80.5 280 PCS100 19-28D-B4C
29 2200x(2041+2041)x703 2800 4350 83.4 290 PCS100 19-29D-C
5
4C
30 2200x(2041+2041)x703 2870 4500 86.3 300 PCS100 19-30D-C
5
4C
31 2200x(2041+2041)x703
2940
4650 89.1 310 PCS100 19-31D-C
5
4C
32 2200x(2041+2041)x703
3010
4800 92.0 320 PCS100 19-32D-C
5
4C
Note:
1
Assuming typical additional heating from coupling transformer.
2
T000 option with free space for customer coupling transformer inside the cabinet (does not include transformer).
3
Refer to section 2.1.3 for the right code according the bus bars termination
4
Place C for center termination (2 m rack on the right) or D for center termination (2 m rack on the left)
5
Please consult factory for any systems with over 14 D-type modules on a single two-section rack. Refer to 2.1.3