3 Technical Specification
PCS100 ESS User Manual | 2UCD190000E001 rev. J 15
Maximum, voltage to ground +/- 600Vdc
Note: The PCS100 ESS system is in systems which
will not be subject to impulse voltages exceeding their over-
voltage rating. Suitably rated surge protection devices (SPDs)
should be connected from + and - to earth in applications
where surge voltage may exceed the overvoltage
rating (e.g.: remote connected DC sources).
Circuit protection Circuit breaker or fuse (not included)
3.4 Standards and Certifications
Quality ISO 9001
Marking
Refer to 2UCD200000E801 for UL recognized PCS100 components.
Safety IEC 62103
Electromagnetic compatibility
Emissions CISPR 11 Class A Group 1
Immunity IEC 61000-6-2
Note: Minimum requirements must be met to achieve the
EMC claimed performance at the ESS demarcation point. For-
More information please refer to ABB document.
2UCD190000E006 ESS Transformer Requirements
Performance (Aligned with)
IEEE 519
IEEE 1031-2000
Grid connection/monitoring
(Aligned with)
IEEE 1547
Japanese Grid Code
3.5 Environmental
Operating temperature range 0 °C to 50 °C
Temperature derating Above 40 °C, derate at 2 % load per °C
Operating altitude < 1000 m without derating
Capacity derating with altitude 1 % every 100 m above 1000 m, 2000 m maximum
Inverter cooling forced ventilation
Humidity < 95 %, non-condensing
Pollution degree rating 2
Noise
< 85 dBA @ 2 m
Note: Average from measurements taken all around of a 32 type-
. modules rack @ fully loaded.
Seismic rating Designed to UBC zone 4 (rack only)
3.6 Protection Rating
Rack / Cabinet rating
IP20 / NEMA 1
Note: On Rack systems, the IP rating is characterized by the
inverter modules only. Final protection degree dependent on
application.