4 Sub-Assemblies
PCS100 ESS User Manual | 2UCD190000E001 rev. J 20
1 NC
2 C
3 NO
4
5
6
7
8
9
10
11
12
13
14
15
NC
C
NO
NC
C
NO
0 V
RUN
250 Vac / 30 Vdc
1 A
WARNING
250 Vac / 30 Vdc
1 A
FAULT
250 Vac / 30 Vdc
1 A
START
0 V
STOP / INHIBIT / RESET
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
- +
Customer Monitoring
and Alarm Systems
Remote Control
16
17 17
1818
1919
20 20
2121
22 22
2323
2424
25 25
2626
27 27
2828 PSU OUT -
+
+
+
-
-
-
+
-
PSU OUT +
PSU 2 -
PSU 2 +
PSU 1 -
PSU 1 +
PTC
PTC
Control
Power
Figure 4-6: Remote Control, Monitoring and Control Power Terminals on the PCS100 Compact Master Module
Terminal
Number
Description Name
1 Relay output / 250 Vac/30 Vdc, 1 A / NC RUN Status (Normally Closed)
2 Relay output / 250 Vac/30 Vdc , 1 A / C RUN Status (Common)
3 Relay output / 250 Vac/30 Vdc , 1 A / NO RUN Status (Normally Open)
4 Relay output / 250 Vac/30 Vdc , 1 A / NC WARNING Status (Normally Closed)
5 Relay output / 250 Vac/30 Vdc , 1 A / C WARNING Status (Common)
6 Relay output / 250 Vac/30 Vdc , 1 A / NO WARNING Status (Normally Open)
7 Relay output / 250 Vac/30 Vdc , 1 A / NC FAULT Status (Normally Closed)
8 Relay output / 250 Vac/30 Vdc , 1 A / C FAULT Status (Common)
9 Relay output / 250 Vac/30 Vdc , 1 A / NO FAULT Status (Normally Open)
10 NA 10
11 NA 11
12 Dry contact only: Return Wire 0V Start Input – return
13 Dry contact only: Start on closing edge START Start Input – only used if remote Start
is required
14 Dry contact only: Return Wire 0V Stop/Inhibit/Reset - return
15 Dry contact only: Stop on open edge: Inhibit while
open; Reset on open edge
Stop/Inhibit/Reset – input
16 NA 16
17 NA 17
18 NA 18
19 NA 19
20 NA 20
21 PTC input (e.g. for transformer supervision) PTC
22 PTC input (e.g. for transformer supervision) PTC