04-3598_ABB_PVA11_T_1-3kVA_EN_REV-B.doc Page 19/29 ABB
Modifications reserved
Load
Indicates the load percentage in Watt or Volt-Ampere
Indicates that the output is short circuited and that the UPS could shutdown
Indicates that the load is over the specified range.
Indicates the load percentage. Each grid represents 25% load.
Indicates the load is over the specified range.
Battery
Indicates the battery DC voltage value.
Indicates the battery capacitance percent, and every grid represent 25%
capacitance.
Indicates that the UPS is in the battery mode and that the battery is
discharging.
Indicates that the battery is over charged. In this case, the UPS switches to
Battery mode.
Indicates low battery autonomy.
Mode/Fault/Warning
Indicates the operating mode of the UPS: Mode code, Fault code or Warning
code. For more information on the codes, see Chapter Troubleshooting.
Indicates that the UPS is working in bypass mode.
Indicates absence of power in the output of the UPS.
Indicates that the UPS is working in online mode.
Indicates that the UPS is working in battery mode.
Indicates that the UPS is in fault mode.
Indicates that the UPS is running under warnings.
Indicates a failure which that can be identified by the fault codes in Section 6.
Parameters Selection
The parameters below can be set while the UPS is running or bypass or is turned off.
The user can select one of four output voltages (208, 220, 230 or 240Vac).
Note that there is a 10% de-rating when this voltage is set to 208Vac.
The user can select one of two frequency values for the output (50 or 60z).
The user can enable or disable the bypass of the UPS.