Figure 25: Setting menu tree
If the password is enabled, the user must enter the password USER by pressing the buttons , and
. It is used mainly to protect against modifications in the Settings menu. The possible operations are
indicated in Table 6.
Submenu item Description Optional Values
value
Language Select menu language English / Chinese English
User password* Protects against settings modifications enabled/disabled disabled
Audio alarm Enable/disable alarm sounds enabled/disabled enabled
Output voltage Define local output voltage 200/208/220/230/240V 230V
Output frequency Define local output frequency
autosensing/50/60Hz
UPS detects the frequency
when in ‘autosensing’
autosensing
Power strategy**
mode)/ converter
normal
DC start (Cold start)
Start the UPS from the batteries (without
mains power)
enabled/disabled enabled
Automatic battery
tests period
Define the frequency of the battery tests 0-31 days 7 days
Auto restart
After power outage, the loads restart
automatically when mains power is
recovered.
enabled/disabled enabled
Automatic overload
restart
The UPS is automatically restarted if it
shutdown for overload.
enabled/disabled enabled
Auto bypass
The automatic bypass can be disabled for
countries where the power supply is very
unstable. UPS runs only online or on battery.
enabled/disabled disabled
Short circuit
clearance
- When enabled, short circuit will last for 4s
before cutting off the output. If short circuit is
removed during this time, the UPS will
continue to run normally.
- When disabled, short circuit will only last
enabled/disabled disabled