4NWP100559R0001_OPM_ABB_PVA31-11-T_10-20kVA_EN_140626 Page 31/37 ABB
Modifications reserved
for 100ms before UPS output is cut off.
Bypass voltage low
limit
When the voltage in the bypass is below this
limit, the UPS changes running mode.
176~215V 184V
Bypass voltage high
limit
When the voltage in the bypass is above this
limit, the UPS changes running mode.
245~276V 264V
this limit, the UPS changes running mode.
40~49.5 Hz 45 Hz
this limit, the UPS changes running mode.
50.5~70 Hz 55 Hz
Eco-mode voltage
low limit
When the voltage in the bypass is below this
limit, the UPS changes running mode.
1%~10% 5%
Eco-mode voltage
high limit
When the voltage in the bypass is above this
limit, the UPS changes running mode.
1%~10% 5%
Eco-mode frequency
low limit
When the frequency in the bypass is below
this limit, the UPS changes running mode.
1%~10% 5%
Eco-mode frequency
high limit
When the frequency in the bypass is above
this limit, the UPS changes running mode.
1%~10% 5%
External Battery
modules***
Define the number of external battery
modules.
0 - 97 0
Set running time
Used to reset the UPS running time for tests
purposes.
Day:hour:minute:second
0000:0000:00~9999:23:59:59
Running
time
LCD contrast Change the contrast in the LCD display -5~+5 0
displayed in the menu measurements
enabled/disabled enabled
Table 6: Settings menu information
**Read Section 5.2, before using ECO-mode or converter function.
***Ensure the real battery quantity is same as indicated in the settings not to damage the batteries.
Example: Setting the rated output voltage value (Figure 26).
Figure 26: Setting rated output voltage value