Loop 2
35
Loop 2
Decimal Read Write Variable Data type Comment
hexadecimal hexadecimal name
377 0x0179 0xFE87 .INDS_LOOP2 INT Display loop position
1862 0x0746 0xF8BA .L2_A_VORB BOOL AUTOMATIC mode ready
395 0x018B 0xFE75 .L2_ANA_LO REAL Lower bargraph scaling
397 0x018D 0xFE73 .L2_ANA_HI REAL Upper bargraph scaling
1861 0x0745 0xF8BB .L2_B1 BOOL Change-over ES1/ES2
375 0x0177 0xFE89 .L2_BA_YOUT REAL Output variable feedback signal
1865 0x0749 0xF8B7 .L2_BETART_UM BOOL Request mode change-over
1864 0x0748 0xF8B8 .L2_C_VORB BOOL CASCADE mode ready
847 0x034F 0xFCB1 .L2_D REAL Signal for D of PID
441 0x01B9 0xFE47 .L2_D1 DINT Free DINT variable
443 0x01BB 0xFE45 .L2_D2 DINT Free DINT variable
445 0x01BD 0xFE43 .L2_D3 DINT Free DINT variable
447 0x01BF 0xFE41 .L2_D4 DINT Free DINT variable
301 0x012D 0xFED3 .L2_ES1 REAL 1st. input of input circuit
303 0x012F 0xFED1 .L2_ES2 REAL 2nd. input of input circuit
305 0x0131 0xFECF .L2_ES3 REAL 3rd. input of input circuit
307 0x0133 0xFECD .L2_ES4 REAL 4th. input of input circuit
309 0x0135 0xFECB .L2_ES5 REAL 5th. input of input circuit
1874 0x0752 0xF8AE .L2_GW1_OUT BOOL Violation of limit value L2-LV1
1875 0x0753 0xF8AD .L2_GW2_OUT BOOL Violation of limit value L2-LV2
1876 0x0754 0xF8AC .L2_GW3_OUT BOOL Violation of limit value L2-LV3
1877 0x0755 0xF8AB .L2_GW4_OUT BOOL Violation of limit value L2-LV4
1869 0x074D 0xF8B3 .L2_HAND_M BOOL Step output MORE
1870 0x074E 0xF8B2 .L2_HAND_W BOOL Step output LESS
327 0x0147 0xFEB9 .L2_K1 REAL Evaluation factor K1
329 0x0149 0xFEB7 .L2_K2 REAL Evaluation factor K2
331 0x014B 0xFEB5 .L2_K3 REAL Evaluation factor K3
333 0x014D 0xFEB3 .L2_K4 REAL Evaluation factor K4
967 0x03C7 0xFC39 .L2_K5 REAL Evaluation factor K5
969 0x03C9 0xFC37 .L2_K6 REAL Evaluation factor K6
971 0x03CB 0xFC35 .L2_K7 REAL Evaluation factor K7
973 0x03CD 0xFC33 .L2_K8 REAL Evaluation factor K8
975 0x03CF 0xFC31 .L2_K9 REAL Evaluation factor K9
977 0x03D1 0xFC2F .L2_K10 REAL Evaluation factor K10
979 0x03D3 0xFC2D .L2_K11 REAL Evaluation factor K11
981 0x03D5 0xFC2B .L2_K12 REAL Evaluation factor K12
983 0x03D7 0xFC29 .L2_K13 REAL Evaluation factor K13
985 0x03D9 0xFC27 .L2_K14 REAL Evaluation factor K14
987 0x03DB 0xFC25 .L2_K15 REAL Evaluation factor K15
989 0x03DD 0xFC23 .L2_K16 REAL Evaluation factor K16
349 0x015D 0xFEA3 .L2_KP_STEUER REAL Effective P-gain
351 0x015F 0xFEA1 .L2_KS_STEUER REAL Effective amplification constant Ks
399 0x018F 0xFE71 .L2_LAMBDA REAL
1863 0x0747 0xF8B9 .L2_M_VORB BOOL MAN mode ready
1880 0x0758 0xF8A8 .L2_MAN_AUTO BOOL Controller in AUTO or MAN mode
1881 0x0759 0xF8A7 .L2_MAN_CAS BOOL Controller in CASCADE or MAN mode
365 0x016D 0xFE93 .L2_PID_D_OUT REAL D-portion of output signal
363 0x016B 0xFE95 .L2_PID_I_OUT REAL I-portion of output signal
1878 0x0756 0xF8AA .L2_PID_PS BOOL Change-over parameter set 1<->2
851 0x0353 0xFCAD .L2_PID_Y_OUT REAL Cont. output signal
421 0x01A5 0xFE5B .L2_R1 REAL Free REAL variable
423 0x01A7 0xFE59 .L2_R2 REAL Free REAL variable
425 0x01A9 0xFE57 .L2_R3 REAL Free REAL variable
427 0x01AB 0xFE55 .L2_R4 REAL Free REAL variable
429 0x01AD 0xFE53 .L2_R5 REAL Free REAL variable
431 0x01AF 0xFE51 .L2_R6 REAL Free REAL variable
433 0x01B1 0xFE4F .L2_R7 REAL Free REAL variable
435 0x01B3 0xFE4D .L2_R8 REAL Free REAL variable
1866 0x074A 0xF8B6 .L2_REGLER_AUTO BOOL Controller AUTO
1868 0x074C 0xF8B4 .L2_REGLER_C BOOL Controller CASCADE
1867 0x074B 0xF8B5 .L2_REGLER_MAN BOOL Controller MAN
371 0x0173 0xFE8D .L2_SCAL_LO REAL Lower control loop scaling
373 0x0175 0xFE8B .L2_SCAL_HI REAL Upper control loop scaling
1884 0x075C 0xF8A4 .L2_SETZ_AUTO BOOL Change-over to automatic mode
1885 0x075D 0xF8A3 .L2_SETZ_CASC BOOL Change-over to cascade mode