ABB Protronic 100 - Setpoint Management and Override Control

ABB Protronic 100
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
Loop 1
Decimal Read Write Variable Data type Comment
hexadecimal hexadecimal name
1843 0x0733 0xF8CD .L1_SETZ_MAN BOOL Change-over to man. mode
1049 0x0419 0xFBE7 .L1_SETZ_W INT Change-over to setpoint source
269 0x010D 0xFEF3 .L1_SKALV REAL Scaling factor ratio with LOAD AIR
1839 0x072F 0xF8D1 .L1_SPAKTIV BOOL Auto-configuration active
287 0x011F 0xFEE1 .L1_T1 DINT Free time variable
211 0x00D3 0xFF2D .L1_T1_STEUER REAL Effective delay time T1
289 0x0121 0xFEDF .L1_T2 DINT Free time variable
195 0x00C3 0xFF3D .L1_TIME_DPS_MAN DINT Step output increment [ms]
203 0x00CB 0xFF35 .L1_TN_STEUER REAL Effective integral action time [min]
209 0x00D1 0xFF2F .L1_TT_STEUER REAL Effective dead time Tt [min]
205 0x00CD 0xFF33 .L1_TV_STEUER REAL Effective derivative action time [min]
241 0x00F1 0xFF0F .L1_V REAL Setpoint ratio
1833 0x0729 0xF8D7 .L1_V_F BOOL Fixed value/ratio status
243 0x00F3 0xFF0D .L1_VISTDIGI REAL Actual ratio
257 0x0101 0xFEFF .L1_W_FOLGE REAL Setpoint for slave control in cascade
1832 0x0728 0xF8D8 .L1_W_STATUS BOOL
823 0x0337 0xFCC9 .L1_WAKT REAL Current setpoint
173 0x00AD 0xFF53 .L1_WANA REAL
253 0x00FD 0xFF03 .L1_WANA_SKAL REAL SP bargraph
229 0x00E5 0xFF1B .L1_WCOMPUTER REAL Computer target setpoint
175 0x00AF 0xFF51 .L1_WDIGI REAL Current setpoint
267 0x010B 0xFEF5 .L1_WEXT REAL External setpoint
1842 0x0732 0xF8CE .L1_WEXT_AKTIV BOOL External SP active
231 0x00E7 0xFF19 .L1_WSOLL0 REAL Target setpoint 1
233 0x00E9 0xFF17 .L1_WSOLL1 REAL Target setpoint 2
235 0x00EB 0xFF15 .L1_WSOLL2 REAL Target setpoint 3
237 0x00ED 0xFF13 .L1_WSOLL3 REAL Target setpoint 4
821 0x0335 0xFCCB .L1_WW REAL Effective setpoint
167 0x00A7 0xFF59 .L1_XANA REAL
251 0x00FB 0xFF05 .L1_XANA_SKAL REAL PV bargraph
825 0x0339 0xFCC7 .L1_XDIGI REAL Digital display
829 0x033D 0xFCC3 .L1_XW REAL Control deviation in engineering units
187 0x00BB 0xFF45 .L1_XW_EU REAL Control deviation in engineering units
189 0x00BD 0xFF43 .L1_XW_PRZ REAL Control deviation in %
207 0x00CF 0xFF31 .L1_Y0_STEUER REAL Effective operating point [%]
255 0x00FF 0xFF01 .L1_YCOMPUTER REAL OUT COMPUTER with DDC
197 0x00C5 0xFF3B .L1_YHAND REAL Man. value of output variable
191 0x00BF 0xFF41 .L1_YMAX REAL Max. output value
261 0x0105 0xFEFB .L1_YMAX_BR REAL Override selection for override controller
265 0x0109 0xFEF7 .L1_YMAX_HR REAL Override selection for master controller, MIN. selection
193 0x00C1 0xFF3F .L1_YMIN REAL Min. output value
259 0x0103 0xFEFD .L1_YMIN_BR REAL OUT-Min override selection for override controller
263 0x0107 0xFEF9 .L1_YMIN_HR REAL Override selection for master controller, MAX.
selection
219 0x00DB 0xFF25 .L1_YSRUECK REAL Position feedback
163 0x00A3 0xFF5D .L1_YTRACK REAL OUT tracking signal in AUTO mode
1795 0x0703 0xF8FD .SLH_LOOP1 BOOL Loop 1 in display
796 0x031C 0xFCE4 .WW_LOOP1 INT Index of selected setpoint loop 1