Loop 3
37
Loop 3
Decimal Read Write Variable Data type Comment
hexadecimal hexadecimal name
527 0x020F 0xFDF1 .INDS_LOOP3 INT Display loop position
1904 0x0770 0xF890 .L3_C_VORB BOOL CASCADE mode ready
1902 0x076E 0xF892 .L3_A_VORB BOOL AUTOMATIC mode ready
545 0x0221 0xFDDF .L3_ANA_LO REAL Lower bargraph scaling
547 0x0223 0xFDDD .L3_ANA_HI REAL Upper bargraph scaling
1901 0x076D 0xF893 .L3_B1 BOOL Change-overES1/ES2
525 0x020D 0xFDF3 .L3_BA_YOUT REAL Output variable feedback signal
1905 0x0771 0xF88F .L3_BETART_UM BOOL Request mode change-over
867 0x0363 0xFC9D .L3_D REAL Signal for D of PID
591 0x024F 0xFDB1 .L3_D1 DINT Free DINT variable
593 0x0251 0xFDAF .L3_D2 DINT Free DINT variable
595 0x0253 0xFDAD .L3_D3 DINT Free DINT variable
597 0x0255 0xFDAB .L3_D4 DINT Free DINT variable
451 0x01C3 0xFE3D .L3_ES1 REAL 1st. input of input circuit
453 0x01C5 0xFE3B .L3_ES2 REAL 2nd. input of input circuit
455 0x01C7 0xFE39 .L3_ES3 REAL 3rd. input of input circuit
457 0x01C9 0xFE37 .L3_ES4 REAL 4th. input of input circuit
459 0x01CB 0xFE35 .L3_ES5 REAL 5th. input of input circuit
1914 0x077A 0xF886 .L3_GW1_OUT BOOL Violation of limit value L3-LV1
1915 0x077B 0xF885 .L3_GW2_OUT BOOL Violation of limit value L3-LV2
1916 0x077C 0xF884 .L3_GW3_OUT BOOL Violation of limit value L3-LV3
1917 0x077D 0xF883 .L3_GW4_OUT BOOL Violation of limit value L3-LV4
1909 0x0775 0xF88B .L3_HAND_M BOOL Step output MORE
1910 0x0776 0xF88A .L3_HAND_W BOOL Step output LESS
477 0x01DD 0xFE23 .L3_K1 REAL Evaluation factor K1
479 0x01DF 0xFE21 .L3_K2 REAL Evaluation factor K2
481 0x01E1 0xFE1F .L3_K3 REAL Evaluation factor K3
483 0x01E3 0xFE1D .L3_K4 REAL Evaluation factor K4
991 0x03DF 0xFC21 .L3_K5 REAL Evaluation factor K5
993 0x03E1 0xFC1F .L3_K6 REAL Evaluation factor K6
995 0x03E3 0xFC1D .L3_K7 REAL Evaluation factor K7
997 0x03E5 0xFC1B .L3_K8 REAL Evaluation factor K8
999 0x03E7 0xFC19 .L3_K9 REAL Evaluation factor K9
1001 0x03E9 0xFC17 .L3_K10 REAL Evaluation factor K10
1003 0x03EB 0xFC15 .L3_K11 REAL Evaluation factor K11
1005 0x03ED 0xFC13 .L3_K12 REAL Evaluation factor K12
1007 0x03EF 0xFC11 .L3_K13 REAL Evaluation factor K13
1009 0x03F1 0xFC0F .L3_K14 REAL Evaluation factor K14
1011 0x03F3 0xFC0D .L3_K15 REAL Evaluation factor K15
1013 0x03F5 0xFC0B .L3_K16 REAL Evaluation factor K16
499 0x01F3 0xFE0D .L3_KP_STEUER REAL Effective P-gain
501 0x01F5 0xFE0B .L3_KS_STEUER REAL Effective amplification constant Ks
549 0x0225 0xFDDB .L3_LAMBDA REAL
1903 0x076F 0xF891 .L3_M_VORB BOOL MAN mode ready
1920 0x0780 0xF880 .L3_MAN_AUTO BOOL Controller in AUTO or MAN mode
1921 0x0781 0xF87F .L3_MAN_CAS BOOL Controller in CASCADE or MAN mode
515 0x0203 0xFDFD .L3_PID_D_OUT REAL D-portion of output signal
513 0x0201 0xFDFF .L3_PID_I_OUT REAL I-portion of output signal
1918 0x077E 0xF882 .L3_PID_PS BOOL Change-over parameter set 1<->2
871 0x0367 0xFC99 .L3_PID_Y_OUT REAL Cont. output signal
571 0x023B 0xFDC5 .L3_R1 REAL Free REAL variable
573 0x023D 0xFDC3 .L3_R2 REAL Free REAL variable
575 0x023F 0xFDC1 .L3_R3 REAL Free REAL variable
577 0x0241 0xFDBF .L3_R4 REAL Free REAL variable
579 0x0243 0xFDBD .L3_R5 REAL Free REAL variable
581 0x0245 0xFDBB .L3_R6 REAL Free REAL variable
583 0x0247 0xFDB9 .L3_R7 REAL Free REAL variable
585 0x0249 0xFDB7 .L3_R8 REAL Free REAL variable
1906 0x0772 0xF88E .L3_REGLER_AUTO BOOL Controller AUTO
1908 0x0774 0xF88C .L3_REGLER_C BOOL Controller CASCADE
1907 0x0773 0xF88D .L3_REGLER_MAN BOOL Controller MAN
521 0x0209 0xFDF7 .L3_SCAL_LO REAL Lower control loop scaling
523 0x020B 0xFDF5 .L3_SCAL_HI REAL Upper control loop scaling
1924 0x0784 0xF87C .L3_SETZ_AUTO BOOL Change-over to automatic mode
1925 0x0785 0xF87B .L3_SETZ_CASC BOOL Change-over to cascade mode