38
Loop 3
Decimal Read Write Variable Data type Comment
hexadecimal hexadecimal name
1923 0x0783 0xF87D .L3_SETZ_MAN BOOL Change-over to man. mode
1051 0x041B 0xFBE5 .L3_SETZ_W INT Change-over to setpoint source
569 0x0239 0xFDC7 .L3_SKALV REAL Scaling factor ratio with LOAD AIR
1919 0x077F 0xF881 .L3_SPAKTIV BOOL Auto-configuration active
587 0x024B 0xFDB5 .L3_T1 DINT Free time variable
511 0x01FF 0xFE01 .L3_T1_STEUER REAL Effective delay time T1
589 0x024D 0xFDB3 .L3_T2 DINT Free time variable
495 0x01EF 0xFE11 .L3_TIME_DPS_MAN DINT Step output increment [ms]
503 0x01F7 0xFE09 .L3_TN_STEUER REAL Effective integral action time [min]
509 0x01FD 0xFE03 .L3_TT_STEUER REAL Effective dead time Tt [min]
505 0x01F9 0xFE07 .L3_TV_STEUER REAL Effective derivative action time [min]
541 0x021D 0xFDE3 .L3_V REAL Setpoint ratio
1913 0x0779 0xF887 .L3_V_F BOOL Fixed value/ratio status
543 0x021F 0xFDE1 .L3_VISTDIGI REAL Actual ratio
557 0x022D 0xFDD3 .L3_W_FOLGE REAL Setpoint for slave control in cascade
1912 0x0778 0xF888 .L3_W_STATUS BOOL
863 0x035F 0xFCA1 .L3_WAKT REAL Current setpoint
473 0x01D9 0xFE27 .L3_WANA REAL
553 0x0229 0xFDD7 .L3_WANA_SKAL REAL SP bargraph
529 0x0211 0xFDEF .L3_WCOMPUTER REAL Computer target setpoint %
475 0x01DB 0xFE25 .L3_WDIGI REAL Current setpoint
567 0x0237 0xFDC9 .L3_WEXT REAL External setpoint
1922 0x0782 0xF87E .L3_WEXT_AKTIV BOOL External SP active
531 0x0213 0xFDED .L3_WSOLL0 REAL Target setpoint 1
533 0x0215 0xFDEB .L3_WSOLL1 REAL Target setpoint 2
535 0x0217 0xFDE9 .L3_WSOLL2 REAL Target setpoint 3
537 0x0219 0xFDE7 .L3_WSOLL3 REAL Target setpoint 4
861 0x035D 0xFCA3 .L3_WW REAL Effective setpoint
467 0x01D3 0xFE2D .L3_XANA REAL
551 0x0227 0xFDD9 .L3_XANA_SKAL REAL PV bargraph
865 0x0361 0xFC9F .L3_XDIGI REAL Digital display PV
869 0x0365 0xFC9B .L3_XW REAL Control deviation in engineering units
487 0x01E7 0xFE19 .L3_XW_EU REAL Control deviation in engineering units
489 0x01E9 0xFE17 .L3_XW_PRZ REAL Control deviation in %
507 0x01FB 0xFE05 .L3_Y0_STEUER REAL Effective operating point [%]
555 0x022B 0xFDD5 .L3_YCOMPUTER REAL OUT COMPUTER with DDC
497 0x01F1 0xFE0F .L3_YHAND REAL Man. value of output variable
491 0x01EB 0xFE15 .L3_YMAX REAL Max. output value
561 0x0231 0xFDCF .L3_YMAX_BR REAL Override selection for override controller
565 0x0235 0xFDCB .L3_YMAX_HR REAL Override selection for master controller, MIN. selection
493 0x01ED 0xFE13 .L3_YMIN REAL Min. output value
559 0x022F 0xFDD1 .L3_YMIN_BR REAL OUT-Min override selection for override controller
563 0x0233 0xFDCD .L3_YMIN_HR REAL Override selection for master controller, MAX.
selection
519 0x0207 0xFDF9 .L3_YSRUECK REAL Position feedback
463 0x01CF 0xFE31 .L3_YTRACK REAL OUT tracking signal in AUTO mode
1797 0x0705 0xF8FB .SLH_LOOP3 BOOL Loop 3 in display
798 0x031E 0xFCE2 .WW_LOOP3 INT Index of selected setpoint loop 3