Chapter 10
Functions
10:43 Phase loss fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Ph Loss Op
This parameter makes it possible to select between two different actions if a phase loss fault
occurs.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text Default value Setting range Description
Ph Loss Op Stop-M Stop-M, Stop-A
Type of operation for
phase loss fault
10:44 Fieldbus fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/FB Fault Op
This parameter makes it possible to select between two different actions if a fault occurs in
the eldbus communication.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text Default value Setting range Description
FB Fault Op Stop-M Stop-M, Stop-A
Type of operation for
eldbus fault
10:45 Frequency fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Freq F Op
This parameter makes it possible to select between two different actions if the frequency is
out of range (frequency fault).
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text Default value Setting range Description
Freq F Op Stop-M Stop-M, Stop-A
Type of operation for
frequency fault
10:46 Heatsink over-temperature fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/HS Temp Op
This parameter makes it possible to select between two different actions if the heat sink
temperature of the softstarter is too high.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text Default value Setting range Description
HS Temp Op Stop-M Stop-M, Stop-A
Type of operation for
heat sink overtempera-
ture fault