Questions and Answers

  • C
    Christopher JohnsonSep 23, 2025
    What does 'Faulty usage' mean on my ABB PSTX470 Controller?
    • E
      ejonesSep 23, 2025
      Do not use jog forward, jog backward, heat motor, or stand-still break functions with an Inside delta motor connection.
  • T
    Thomas WalkerAug 25, 2025
    What does it mean when my ABB PSTX470 Controller displays 'Ground fault'?
    • J
      John PotterAug 25, 2025
      A ground fault indicates that the sum of the instantaneous line currents in your 3-phase system differs more than the specified value. Examine the motor cables and the motor itself for any issues.
  • J
    Joshua PerezAug 25, 2025
    What should I do if my ABB PSTX470 displays 'Locked rotor'?
    • K
      Kevin KirkAug 26, 2025
      Examine the bearings of the motor and the load to ensure they run easily. A damaged bearing or a load stock could be the cause.
  • M
    Michelle BeckerAug 27, 2025
    What does it mean when my ABB PSTX470 Controller displays 'Overvoltage'?
    • J
      Jose CastroAug 27, 2025
      An overvoltage error indicates that the main voltage is too high. Perform a check of the main voltage.
  • D
    Dana ClarkAug 27, 2025
    What does it mean when my ABB Controller displays 'Under voltage'?
    • T
      Tonya MunozAug 27, 2025
      An undervoltage error indicates that the main voltage is too low. Perform a check of the main voltage.
  • R
    rglassSep 14, 2025
    What does 'High current' mean on my ABB PSTX470 Controller?
    • A
      Amber CarrollSep 15, 2025
      A high current fault indicates that a fault current, higher than 8 times the softstarter's rated current, has occurred. Check the circuits and the motor for an insulation fault between phases or a ground fault.
  • M
    Mrs. Victoria WilliamsSep 12, 2025
    What does 'Voltage imbalance' mean on my ABB PSTX470 Controller?
    • B
      Brittany MooreSep 12, 2025
      Voltage imbalance indicates that there is a voltage imbalance between the phases. Check the main voltage and restart the motor.
  • S
    Seth LongSep 13, 2025
    Why does my ABB Controller display 'Too long start time'?
    • W
      William BarrettSep 13, 2025
      This indicates that the time taken to soft start the motor is longer than the set value. Check the starting conditions and current limit.
  • J
    John TorresSep 4, 2025
    How do I fix an ABB PSTX470 Controller that shows a blank screen and no LED is active?
    • E
      Emily GrossSep 4, 2025
      First, ensure that the supply voltage is properly connected, referring to the circuit diagram. Also check that the RJ45 plug is connected between the HMI and the softstarter, and that the RJ45 network cable is not damaged.
  • A
    ashley93Sep 2, 2025
    What to do if my ABB PSTX470 Controller motor is humming or starts without a given start signal?
    • D
      David SandersSep 2, 2025
      This issue could be due to a few reasons. If it's a PSTX30...170 model, a bypass relay might be closed due to inaccurate handling. To resolve this, disconnect the operation voltage and the control supply voltage, remove the USB cable if connected, and then reconnect the voltage in the following sequence: first, the control supply voltage on terminals 1 and 2 (refer to chapter 5.1.2), wait 4 seconds, and then connect the operation voltage on terminals L1, L2, and L3. Alternatively, the bypass contactor/relay could be stuck in a closed position, or there might be a shorted thyristor. In either of these cases, it is best to speak to your ABB Sales Office.

Summary

Read this first

Description

Mounting

Connection

Human Machine Interface HMI

Softstarter settings

First start-up

Guides the user through initial setup and configuration of the softstarter.

Assistants menu

Details the step-by-step wizard for initial configuration tasks.

Troubleshooting

Contact us

ABB PSTX470 Specifications

General IconGeneral
TypeSoftstarter
Output Voltage220-690V AC
Rated Operational Current - In Line Connection (Ie)470 A
Rated Power - In Line Connection 690V560 kW
Weight22 kg
Control MethodVoltage ramp
Protection FeaturesOverload, Phase loss
Communication ProtocolModbus RTU
Operating temperature range-25°C to +60°C
Input Voltage208 ... 690 V AC
Input voltage range220-690V AC