Questions and Answers

  • E
    Elizabeth CaseySep 23, 2025
    What does 'Faulty usage' mean on my ABB PSTX142 Controller?
    • R
      Robert WillisSep 23, 2025
      Do not use jog forward, jog backward, heat motor, or stand-still break functions with an Inside delta motor connection.
  • H
    Hannah BrooksAug 25, 2025
    What does it mean when my ABB PSTX142 displays 'Ground fault'?
    • K
      Kathy SmithAug 25, 2025
      A ground fault indicates that the sum of the instantaneous line currents in your 3-phase system differs more than the specified value. Examine the motor cables and the motor itself for any issues.
  • V
    vargasryanAug 25, 2025
    What should I do if my ABB PSTX142 Controller displays 'Locked rotor'?
    • M
      Michael SheppardAug 26, 2025
      Examine the bearings of the motor and the load to ensure they run easily. A damaged bearing or a load stock could be the cause.
  • C
    charles71Aug 27, 2025
    What does it mean when my ABB PSTX142 displays 'Overvoltage'?
    • J
      John SmithAug 27, 2025
      An overvoltage error indicates that the main voltage is too high. Perform a check of the main voltage.
  • E
    elizabeth07Aug 27, 2025
    What does it mean when my ABB Controller displays 'Under voltage'?
    • C
      Christopher HowardAug 27, 2025
      An undervoltage error indicates that the main voltage is too low. Perform a check of the main voltage.
  • B
    benjamin16Sep 15, 2025
    What does 'High current' mean on my ABB Controller?
    • B
      bryan33Sep 15, 2025
      A high current fault indicates that a fault current, higher than 8 times the softstarter's rated current, has occurred. Check the circuits and the motor for an insulation fault between phases or a ground fault.
  • R
    Raymond MayerSep 12, 2025
    What does 'Voltage imbalance' mean on my ABB PSTX142?
    • L
      Lindsey BlackburnSep 12, 2025
      Voltage imbalance indicates that there is a voltage imbalance between the phases. Check the main voltage and restart the motor.
  • H
    haydenrichardSep 13, 2025
    Why does my ABB PSTX142 Controller display 'Too long start time'?
    • M
      Maxwell SmithSep 13, 2025
      This indicates that the time taken to soft start the motor is longer than the set value. Check the starting conditions and current limit.
  • T
    Tina WillisSep 4, 2025
    How do I fix an ABB PSTX142 that shows a blank screen and no LED is active?
    • A
      alan34Sep 4, 2025
      First, ensure that the supply voltage is properly connected, referring to the circuit diagram. Also check that the RJ45 plug is connected between the HMI and the softstarter, and that the RJ45 network cable is not damaged.
  • R
    Ryan FosterSep 2, 2025
    What to do if my ABB PSTX142 motor is humming or starts without a given start signal?
    • A
      Alexandra PetersonSep 2, 2025
      This issue could be due to a few reasons. If it's a PSTX30...170 model, a bypass relay might be closed due to inaccurate handling. To resolve this, disconnect the operation voltage and the control supply voltage, remove the USB cable if connected, and then reconnect the voltage in the following sequence: first, the control supply voltage on terminals 1 and 2 (refer to chapter 5.1.2), wait 4 seconds, and then connect the operation voltage on terminals L1, L2, and L3. Alternatively, the bypass contactor/relay could be stuck in a closed position, or there might be a shorted thyristor. In either of these cases, it is best to speak to your ABB Sales Office.

Summary

1 Read this first

3 Mounting

Mounting Procedures and HMI Installation

Step-by-step guide for installing the softstarter and HMI.

4 Connection

Main Circuit Wiring

Instructions for connecting the main power terminals (L1, L2, L3, T1, T2, T3).

Control and Input Connections

Covers control supply, earth, start/stop, and input terminal connections.

6 Softstarter Settings

Initial Setup Assistant

Guides users through basic and application setup with a step-by-step wizard.

Motor Data Configuration

Details setting the motor rated current for different connection types.

8 Short Circuit Current Ratings

7 Troubleshooting

Motor and Phase Fault Diagnosis

Diagnoses issues like overload, locked rotor, phase reversal, and current imbalance.

ABB PSTX142 Specifications

General IconGeneral
Rated operational current, Ie142 A
Starting methodSoft starter
IP RatingIP20
Output current142 A
Weight5.5 kg
Rated operational voltage208 ... 690 V
CommunicationModbus RTU
Operating temperature-25 to +60 °C