Softstarters Type PSTX30...PSTX570
User Manual short form
1SFC132082M9901

Other manuals for ABB PSTX142

Questions and Answers

  • V
    Valerie Graves DDSSep 10, 2025
    What does 'Phase reversal' mean on my ABB PSTX142 Controller?
    • L
      Laura WrightSep 10, 2025
      Phase reversal indicates that the phase sequence is incorrect, leading to current imbalance between the phases. To correct this, change the phase sequence on the line side to (L1-L2-L3). Then, restart the motor and check the main currents and voltage.
  • M
    Michael GoodSep 7, 2025
    Why does my ABB Controller motor make a bad sound during both start and stop?
    • N
      Nicole KingSep 8, 2025
      This could be due to several factors. First, try different settings for the Initial/End Voltage parameter. Also, experiment with different settings for the Current limit level or Torque limit level parameters. Ensure that you have the correct softstarter for the motor size. Make sure that the start and stop commands are not given at the same time. Check that the operation voltage is not below 175 V.
  • R
    ronald10Sep 6, 2025
    What to do if loading parameters with Fieldbus does not work correctly on my ABB PSTX142?
    • W
      Wendy MillerSep 7, 2025
      Ensure that the parameters match between the PLC and the Softstarter Fieldbus documentation for the used Fieldbus protocol. Make sure that the Auto mode bit of the binary output telegram setting is 1. Check if the HMI is set to remote control. Ensure that the Local Mode digital input on the ABB FieldBus Plug adapter is set to Remote. Make sure that Fieldbus disable control in DI is not connected. Verify that the Fieldbus control parameter is set to On.
  • T
    thomas29Aug 22, 2025
    What causes an electronic overload in my ABB PSTX142 and how can I resolve it?
    • T
      Terri DaughertyAug 23, 2025
      An electronic overload occurs when the motor current is too high for an extended period, often due to a high load on the motor shaft. To resolve this: * Examine start conditions and EOL settings. * Correct the reason for the overload. * Ensure the current limit level is not set too low. * Verify the ramp time for start is not too long. * Confirm the correct overload class is used. * Check that the Setting Ie parameter is correct.
  • T
    Tina WillisSep 4, 2025
    How do I fix an ABB PSTX142 that shows a blank screen and no LED is active?
    • A
      alan34Sep 4, 2025
      First, ensure that the supply voltage is properly connected, referring to the circuit diagram. Also check that the RJ45 plug is connected between the HMI and the softstarter, and that the RJ45 network cable is not damaged.
  • J
    Jessica WalkerSep 3, 2025
    Why is my ABB PSTX142 Controller showing a dark screen but the LED is active?
    • K
      Kristen TranSep 3, 2025
      The controller is likely in power save mode. Simply touch a key on the keypad to exit this mode.
  • R
    Ryan FosterSep 2, 2025
    What to do if my ABB PSTX142 motor is humming or starts without a given start signal?
    • A
      Alexandra PetersonSep 2, 2025
      This issue could be due to a few reasons. If it's a PSTX30...170 model, a bypass relay might be closed due to inaccurate handling. To resolve this, disconnect the operation voltage and the control supply voltage, remove the USB cable if connected, and then reconnect the voltage in the following sequence: first, the control supply voltage on terminals 1 and 2 (refer to chapter 5.1.2), wait 4 seconds, and then connect the operation voltage on terminals L1, L2, and L3. Alternatively, the bypass contactor/relay could be stuck in a closed position, or there might be a shorted thyristor. In either of these cases, it is best to speak to your ABB Sales Office.
  • C
    Colton HendersonSep 1, 2025
    How to troubleshoot phase loss in ABB PSTX142?
    • L
      Lawrence MorenoSep 1, 2025
      Check that the mains are connected and that no line contactor or breaker is open. Inspect the fuses for all 3 phases, replacing any that are blown. Verify the operation network supply and correct it if there's a power loss on one or multiple phases. Ensure the contactor/breaker or external switch device is closed. If the line contactor opens too quickly at stop, control it with the Run signal relay on terminal 4, adding a time relay before the contactor opens. If Stop Ramp is not necessary, set Stop mode to direct stop.
  • A
    Alan WoodAug 30, 2025
    What to do if my ABB PSTX142 motor does not start when given a start command by the hardwire inputs?
    • E
      erin90Aug 31, 2025
      First, check the connections for start and stop. Make sure that the start and stop commands are not given at the same time. Ensure that the keypad is not in Local Control mode; if it is, push the R\L-key to change to Remote Control mode. Also, verify that the Fieldbus control parameter is set to No. Finally, reset any active or tripping events.
  • A
    Ashley ReeseAug 29, 2025
    What does 'Thyristor overload' mean on my ABB PSTX142?
    • J
      james19Aug 30, 2025
      A thyristor overload indicates that the thyristors are too hot. Check the start conditions and the fans. If possible, decrease the current limit. Allow the temperature of the thyristors to decrease before restarting.

Summary

1 Read this first

3 Mounting

Mounting Procedures and HMI Installation

Step-by-step guide for installing the softstarter and HMI.

4 Connection

Main Circuit Wiring

Instructions for connecting the main power terminals (L1, L2, L3, T1, T2, T3).

Control and Input Connections

Covers control supply, earth, start/stop, and input terminal connections.

6 Softstarter Settings

Initial Setup Assistant

Guides users through basic and application setup with a step-by-step wizard.

Motor Data Configuration

Details setting the motor rated current for different connection types.

8 Short Circuit Current Ratings

7 Troubleshooting

Motor and Phase Fault Diagnosis

Diagnoses issues like overload, locked rotor, phase reversal, and current imbalance.

ABB PSTX142 Specifications

General IconGeneral
Rated operational current, Ie142 A
Starting methodSoft starter
IP RatingIP20
Output current142 A
Weight5.5 kg
Rated operational voltage208 ... 690 V
CommunicationModbus RTU
Operating temperature-25 to +60 °C