7 - Appendix
Type code PVI-5000-OUTD-US PVI-6000-OUTD-US
Input side
Nominal output power 5000W 6000W
Maximum output power 5000W 6000W
Rated grid AC voltage 208V 240V 277V 208V 240V 277V
Input side (DC)
Number of independent MPPT channels 2
Maximum usable power for each channel 4000W
Absolute maximum voltage (Vmax) 600V
Start-up voltage (Vstart) 200V (adj. 120-350)
Full power MPPT voltage range 200 - 530V
Operating MPPT voltage range 0.7 x Vstart - 580V
Maximum current (Idcmax) for both MPPT in parallel 36A
Maximum usable current per channel 22A
Number of wire landing terminals per channel 2 Pairs
Array wiring termination Terminal block, pressure clamp, AWG16-AWG6
Output side (AC)
Grid connection type 1Ø/2W Split-Ø/3W 1Ø/2W 1Ø/2W Split-Ø/3W 1Ø/2W
Adjustable voltage range (Vmin-Vmax) 183V-228V 221V-264V 244V-304V 183V-228V 211V-264V 244V-304V
Grid frequency 60Hz
Adjustable grid frequency range 57-60.5Hz
Maximum current (I
ac,max
) A
RMS
27A
RMS
23A
RMS
20A
RMS
30A
RMS
28A
RMS
24A
RMS
Power factor > 0.995
Total harmonic distortion at rated power < 2%
Contributory fault current
1
36.25 A
pk
/
25.63A
RMS
36.5 A
pk
/
25.81A
RMS
31.75 A
pk
/
22.45A
RMS
36.25 A
pk
/
25.63A
RMS
36.5 A
pk
/
25.81A
RMS
31.75 A
pk
/
22.45A
RMS
Grid wiring termination type Terminal block, pressure clamp, AWG14-AWG4
Input
Reverse polarity protection Yes
Over-voltage protection type Varistor, 2 for each channel
PV array ground fault detection Pre start-up Riso and Dynamic GFDI (requires floating arrays)
Output
Anti-islanding protection Meets UL 1741/IEEE1547 requirements Meets UL 1741/IEEE1547 requirements
Over-voltage protection type Varistor, 2
(L
1
- L
2
/ L
1
- G)
Varistor, 2
(L
1
- L
2
/ L
1
- G)
Maximum AC OCPD Rating 35A 30A 25A 40A 35A 30A
Efficiency
Maximum efficiency 97.1%
CEC efficiency 96% 96.5% 96.5% 96% 96.5% 96.5%
User interface Graphic display Graphic display
Operating performance
Stand-by consumption <8W
RMS
<8W
RMS
Night time consumption <0.6W
RMS
<0.6W
RMS
Communication
User-interface 16 characters x 2 lines LCD display
Remote monitoring (1xRS485 incl.) VSN700 Data Logger (opt)
Wired local monitoring (1xRS485 incl.) PVI-USB-RS485_232 (opt.)
Environmental
Ambient air operating temperature range -13°F to +140°F (-25°C to +60°C)
-13°F to +140°F (-25°C to +60°C) with
derating above 122°F (50°C)
Ambient air storage temperature range -40°F to +176°F (-40°C to +80°C) -40°F to +176°F (-40°C to +80°C)
Relative humidity 0-100% RH condensing 0-100% RH condensing
Acoustic noise emission level < 50 db (A) @1m < 50 db (A) @1m
Maximum operating altitutde without derating 6560 ft (2000 m) 6560 ft (2000 m)
Mechanical specifications
Enclosure rating NEMA 4X
Cooling Natural convection
Dimensions (H x W x D) 41.4x12.8x8.6 in (1052 x 325 x218 mm)
Weight <59.5lb (27.0 kg)
Shipping weight < 78lb (35.4 kg)
Mounting system Wall bracket
Conduit connections
Trade size KOs: (2ea x 1/2”)
and (2ea x 1-1/4”,3 places side, front, rear)
DC switch rating (per contact) 25A / 600V
Safety
Isolation level Transformerless (floating array)
Safety and EMC standard
UL1741, IEE1547, IEE1547.1, CSA-C22.2N. 107.1-01, UL1998 UL 1699B, FCC Part 15
Class B
Safety Approval
c
CSA
us
Warranty
Standard warranty 10 years
Extended warranty 15 & 20 years
Available models
Standard - with DC switch - floating Array PVI-5000-OUTD-US PVI-6000-OUTD-US
With DC switch, wiring box and arc fault detector and
interruptor
PVI-5000-OUTD-US-A PVI-6000-OUTD-US-A
*All data is subject to change without notice
1. Inverter can apply that much current - Breaker will open