Section 2 1MRK 505 350-UEN
Signals
18 Technical Manual
Distributed busbar protection REB500
respectively (CIM module Ethernet ports LAN1 and LAN2). The
signal is active if a link has been established.
Signals the blocking of BBP or the
zone. This signal is a combined signal i.e. both the blocking of BBP
and also blocking of the inter
tripping system are signaled.
Table 19 CU output signals for protection functionality
Signal Description
A fault was detected on phase L0, L1, L2, or L3, respectively, and
BBP has tripped.
42330_Check_Zone_Operated
BBP is blocked (either individual protection zones or the entire
42805_ Check Zone Bypassed
zone release function for BBP is bypassed.
42810_Check_Zone_Diff_Alarm
The differential currents of the check
zone exceed the set alarm
level.
BFP tripped in time step 1.
BFP tripped in time step 2.
BFP is blocked (either a bay unit or the entire system).
EFP is blocked (either a bay unit or the entire system).
OCDT is blocked (either a bay unit or the entire system).
overcurrent functions has picked up.
PDF is blocked (either individual bays or the entire system).
UV has been activated (either individual bays or throughout the
system).
protection functions are blocked (either
individual bays or throughout the system).
Certain bay protection output signals in specific bays or throughout
the entire system are blocked (Must be configured together with the
corresponding BU output signal 29410_BP partial blocked).
The following signals (out of Table 18 and Table 19) can be used to trigger a
disturbance record in the central unit:
• 41815_Diff. current alarm
• 42305_BBP trip