1MRK 505 353-UEN Section 3
Configuring bay protection using HMI500
Application Manual 23
Bay protection functions REB500
Figure 9 Status indication of BP Function
Table 39 Status indication of BP Function – Mode
Dialogue tem Description
The dialog is in the protection function configuration or setting mode.
The dialog was started in the measurement
Not implemented in this version.
The user can edit and save settings.
The user cannot edit settings.
Table 40 Status indication of BP Function – Statistics
Dialogue item Description
Number of instances created by the user for this bay unit. The maximum
number is 128.
The number of memory locations available for protection function settings
protection function settings used by the present bay unit.
3.4 Binary signal configuration
3.4.1.1 Configuring binary input signals
Each Bay protection function has a defined number of binary inputs. These are de-
scribed for each of the protection functions in Section 2.3.2.3. .