58
1MRS750527-MUM
)HHGHU7HUPLQDO
Technical Reference Manual, General
5()B
The following values are recommended for the resistor Rh
ext
in Figure 4.1.11.-1
below:
)LJ 2SHUDWLQJSULQFLSOHRIWKHWULSFLUFXLWVXSHUYLVLRQ7&6IXQFWLRQ
7HUPLQDOQXPEHUVDUHUHODWHGWR+632
 &RQILJXULQJWKHWULSFLUFXLWVXSHUYLVLRQ&07&6B
The Relay Configuration Tool can be used to connect the trip circuit supervision
input status signals to the function blocks CMTCS1 and CMTCS2. The
configuration of the blocking signal is user-specific and can only be defined in the
feeder terminal configuration. The trip circuit supervision inputs in the feeder
terminal configuration are as follows:
TCS1 and TCS2 inputs in REF 541 and REF 543:
TCS1 and TCS2 inputs in REF 545:
2SHUDWLQJYROWDJH8F
6KXQWUHVLVWRU5K
H[W
48 V dc
1.2 k
, 5 W
60 V dc
5.6 k
, 5 W
110 V dc
22 k
, 5 W
220 V dc
33 k
, 5 W
this contact is optional
**) This N/C contact enables supervision of N/O AUX contact;
*) This is the Circuit Breaker N/O AUX contact
**)
*)
+ Uc (Operating voltage)
Ic
> 20 V
REF 54_
Rs
Rh (ext)
Rh (int)
X4.1.13
X4.1.12
X4.1.11
X4.1.10
TCSfunc
Uc
Trip Circuit Supervision 1 input PS1_4_TCS1
Trip Circuit Supervision 2 input PS1_4_TCS2
Trip Circuit Supervision 1 input PS2_4_TCS1
Trip Circuit Supervision 2 input PS2_4_TCS2

Table of Contents

Other manuals for ABB REF 54 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF 54 Series and is the answer not in the manual?

ABB REF 54 Series Specifications

General IconGeneral
BrandABB
ModelREF 54 Series
CategoryTouch terminals
LanguageEnglish

Related product manuals