Table 89. Voltage vector shift protection (VVSPPAM) main settings
Parameter Function Value (Range) Step
Start value VVSPPAM 2.0...30.0° 0.1
Over Volt Blk value VVSPPAM 0.40...1.50 × Un 0.01
Under Volt Blk value VVSPPAM 0.15...1.00 × Un 0.01
Phase supervision VVSPPAM 7 = Ph A + B + C
8 = Pos sequence
-
Generator and Interconnection Protection