M12700-1 v4
Table 136. Event list
Function Value
Buffer capacity Maximum number of events in the list 1000
Resolution 1 ms
Accuracy Depending on time synchronizing
M13765-1 v5
Table 137. Indications
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
Maximum number of recorded disturbances 100
M12702-1 v4
Table 138. Event recorder
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on time
synchronizing
M13747-1 v5
Table 139. Trip value recorder
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
M12384-1 v7
Table 140. Disturbance recorder
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 352
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 141. Event counter with limit supervision L4UFCNT
Function Range or value Accuracy
Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -