Binary input/output modules Ordering no #10 Notes and rules
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM required in slots P3 and P4.
Slot position (front/rear view)
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
These black marks indicate the
maximum number of modules per
casing type and the slots that can
be occupied.
1/2 Case with 1 TRM █ █ █ Only for A20
3/4 Case with 2 TRM █ █ █ █ █ Only for B30/C30
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █ Only for B30/C30
Compression terminals 1MRK002960-KA C
No board in slot X X X X X X X X X
Binary output module 24
output relays (BOM)
1MRK000614-AB A A A A A A A A A A Maximum 4 (BOM+SOM+MIM)
boards.
BIM 16 inputs, RL24,
24-30VDC, 50mA
1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
BIM 16 inputs, RL48,
48-60VDC, 50mA
1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
BIM 16 inputs, RL110,
110-125VDC, 50mA
1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
BIM 16 inputs, RL220,
220-250VDC, 50mA
1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
BIM 16 inputs, RL220,
220-250VDC, 120mA
1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
BIM 16 inputs, RL24,
24-30VDC, 50mA, enhanced
pulse counting
1MRK000508-HA F F F F F F F F F
BIM 16 inputs, RL48,
48-60VDC, 50mA, enhanced
pulse counting
1MRK000508-EA G G G G G G G G G
BIM 16 inputs, RL110,
110-125VDC, 50mA,
enhanced pulse counting
1MRK000508-FA H H H H H H H H H
BIM 16 inputs, RL220,
220-250VDC, 50mA,
enhanced pulse counting
1MRK000508-GA K K K K K K K K K
IOM 8 inputs, 10+2 outputs,
RL24, 24-30VDC, 50mA
1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2 outputs,
RL48, 48-60VDC, 50mA
1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1
IOM 8 inputs, 10+2 outputs,
RL110, 110-125VDC, 50mA
1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1
IOM 8 inputs, 10+2 outputs,
RL220, 220-250VDC, 50mA
1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1
IOM8 inputs 10+2 outputs,
RL220, 220-250VDC, 110mA
1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2
IOM with MOV 8 inputs, 10+2
outputs, RL24, 24-30VDC,
50mA
1MRK000173-GC U U U U U U U U U
IOM with MOV 8 inputs, 10+2
outputs, RL48, 48-60VDC,
50mA
1MRK000173-AD V V V V V V V V V
IOM with MOV 8 inputs, 10+2
outputs, RL110, 110-125VDC,
50mA
1MRK000173-BD W W W W W W W W W
IOM with MOV 8 inputs, 10+2
outputs, RL220, 220-250VDC,
50mA
1MRK000173-CD Y Y Y Y Y Y Y Y Y
mA input module MIM 6
channels
1MRK000284-AB R R R R R R R R R MIM not in A20, Maximum 1 MIM
board in 1/2 case.
SOM Static binary output, 12
outputs; 6 standard relays + 6
static outputs, 48-60VDC
1MRK002614-BA T1 T1 T1 T1 T1 T1 T1 T1 SOM must not be placed in the
following positions: 1/2 case slot
P5, 3/4 case 2 TRM slot P7, 1/1
case 2 TRM slot P13.
SOM Static binary output, 12
outputs; 6 standard relays + 6
static outputs, 110-250VDC
1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2
Selection for
position #10
C
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 137