Maximum 176 binary input channels may
be activated simultaneously with inuencing
factors within nominal range.
M50609-2 v7
Table 16. BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter Settable 1-20 ms
Maximum 176 binary input channels may
be activated simultaneously with inuencing
factors within nominal range.
M12573-1 v9
Table 17. IOM - Binary input/output module
Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency 10 pulses/s max
Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter Settable 1-20 ms