EasyManua.ls Logo

ABB REG670 - Page 79

ABB REG670
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Table 67. Voltage-restrained time overcurrent protection VRPVOC
Function Range or value Accuracy
Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, overcurrent > 95% -
Operate time, start overcurrent at 0 to 2 x I
set
Min. = 15 ms -
Max. = 30 ms
Reset time, start overcurrent at 2 x I
set
to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 x
I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start overcurrent at 10 x I
set
to 0 Min. = 20 ms
Max. = 35 ms
-
Independent time delay to operate at 0 to 2 x
I
set
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Inverse time characteristics,
see tables 172 and 173
13 curve types See tables 172 and 173
Minimum operate time for inverse time
characteristics
(0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
High voltage limit, voltage dependent
operation
(30.0 - 100.0)% of UBase ±1.0% of U
r
Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of U
r
Reset ratio, undervoltage < 105% -
Operate time start undervoltage at 2 x U
set
to
0
Min. = 15 ms -
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x U
set
Min. = 15 ms -
Max. = 30 ms
Independent time delay to operate,
undervoltage at 2 x U
set
to 0
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of U
r
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Undervoltage:
Critical impulse time
Impulse margin time
10ms typically at 2 x U
set
to 0
15 ms typically
-
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 79

Other manuals for ABB REG670

Related product manuals