GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2
Table 92. Number of AND instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
AND 60 60 160
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2
Table 93. Number of GATE instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
GATE 10 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v2
Table 94. Number of INV instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INV 90 90 240
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v1
Table 95. Number of LLD instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v3
Table 96. Number of OR instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
OR 78 60 160
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
Table 97. Number of PULSETIMER instances
Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms
GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v1
Table 98. Number of RSMEMORY instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
Table 99. Number of SRMEMORY instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
1MRK 502 074-BEN A
Generator protection REG670 2.2 and Injection equipment REX060,
REX061, REX062
Product version: 2.2.1
ABB 95