EasyManua.ls Logo

ABB REJ601 - Document Symbols and Conventions

ABB REJ601
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Feeder protection and control / Feeder protection
1MDB07221-YN
REF601 / REJ601
Product version: 2.2 FP2
Issued: 2017-05-09
Revision: A
12 ABB
Table 16. Electromagnetic compatibility tests, continue
Description
Type test value
Reference
Power frequency magnetic field immunity
test:
Continuous
Short duration ( 1 s )
100 A/m
1000 A/m
IEC 61000-4-8
Conducted radio frequency interference
tests:
10 V
f=150 KHz...80 Mhz
IEC 60255-22-6, class III
IEC 61000-4-6
AC Voltage dips and short interruptions:
30% / 25 period
60% / 10 periods
100% / 2.5 periods
100% / 250 periods
IEC 61000-4-11
DC Voltage dips and short interruptions
30% / 500 ms
60% / 200 ms
100% / 50 ms
100% / 5000 ms
IEC 61000-4-29
Power frequency immunity test:
Common mode
Differential mode
300 V rms
150 V rms
IEC 60255-22-7, Class A
Pulse magnetic field immunity tests:
1000 A/m, 6.4/16 μs
IEC 61000-4-9
Emission tests:
Conducted
150 kHz-0.5 MHz
0.5 MHz-30 MHz
Radiated
30-230 MHz
230-1000 MHz
< 66 dB ( μV/m)
< 60 dB ( μV/m)
< 40 dB ( μV/m)
< 47 dB ( μV/m)
IEC 60255-25
EN 55011-CISPR II
Table 17. Insulation tests
Description
Type test value
Reference
Dielectric test
Test voltage
2 kV, 50 Hz, 1 min
IEC 60255-5
IEC 60255-27
Impulse voltage test
Test voltage
5 kV, 1.2/50 μs, 0.5 J
IEC 60255-5
IEC 60255-27
Insulation resistance test
Isolation resistance
> 100 M Ω at 500 V DC
IEC 60255-5
IEC 60255-27

Other manuals for ABB REJ601