Feeder protection and control / Feeder protection
1MDB07221-YN
REF601 / REJ601
Product version: 2.2FP2
Issued: 2017-05-09
Revision: A
9 ABB
Table 8. Binary input
Description
Value
Rated voltage
24...240 V AC / DC
Operating range
85...110% of Un for AC and
70...120% of Un for DC
Current drain
2...20 mA
Power consumption/input
<0.5 W
Input sensing time
25 ms
Trip-circuit supervision (TCS): (BI2)
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
48...250 V AC / DC
~ 1.5 mA
20V AC / DC (15...20 V)
Table 9. Double-pole power output (XK2 : BO2)
Description
Value
Rated voltage
240 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40
ms, at 48/110/220 V DC
(two contacts connected in series)
5 A / 3 A / 1 A
Minimum contact load
100 mA at 24 V AC/DC
Table 10. Single-pole power output relay (XK10 : BO1)
Description
Value
Rated voltage
240 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40
ms, at 35 / 220 V DC
5 A/ 0.2 A
Minimum contact load
100 mA at 24 V AC/DC