I.L. 40-386.12
2-12
2
Output Contact 1 Configuration Output 1 Out_1 None
In-Progress
HLDB
HBDL
HLDB/HBDL
SYNC
HLDB/HBDL/SYNC
In-Progress
Output Contact 2 Configuration Output 2 Out_2 None
Failed Close
HLDB
HBDL
HLDB/HBDL
SYNC
HLDB/HBDL/SYNC
Failed Close
Remote Setting Change Enable Remote Set Remote Set No / Yes Yes
*
*
*
*
Manual Close (settings below
available when Man Close set to
Yes)
- Manual Close on HLDB
- Manual Close on HBDL
- Manual Close if Synchronism
- Manual Max Wait Time for a
HLDB, HBDL or Synchronism
Condition
(Man HLDB, HBDL or Sync must
be “yes” to view this setting)
Man Close
Man HLDB
Man HBDL
Man SYNC
Man Wait
Man Close
Man HLDB
Man HBDL
Man SYNC
Man Wait
No / Yes
No / Yes
No / Yes
No / Yes
0-99 in 1 Second steps
100-990 in 10 Second steps
Infinite Time (No Time Limit)
No
No
No
No
60 sec
Recloser Enable/Disable Recloser Recl Enable Disabled/Enabled Enabled
Table 2-6: RECLOSING SETTINGS WITH RANGES (Sheet 4 of 4)
Setting
Function
Display
RCP
Display
Value
Displayed
Factory
Default
* Settings available only with synchronism check option and when Sync Set? = Yes