I.L. 40-386.12
2-11
2
* - Reclose 4 on HBDL Recl4 HBDL Recl n HBDL No / Yes No
* - Reclose4 on Synchronism Recl4 Sync Recl n Sync No / Yes No
* - 4 Max Wait Time for a HLDB,
HBDL or Synchronism condition.
(Recl4 HLDB, HBDL or Sync
must be “yes” to view this set-
ting)
Recl4 Wait Recl n Wait 0 - 99 Step 1 sec
100 - 990 Step 10 sec
No time Limit (Infinite Time)
60 sec
Fail Reclose Enable FailRecl ? Fail Recl No / Yes Yes
Fail Reclose Max Close Duration
(Not displayed if Fail Recl? = No)
Fail Time Fail Time 1 - 99 Step 1 sec
100 - 250 Step 10 sec
10 sec
Close Contact Duration
(Not displayed if Fail Recl? =
Yes)
ClosePulse ClosePulse 0.01 - 0.99 Step 1 sec
1.0 - 2.0 Step 0.1 sec
0.50 sec
Reset Duration Reset Time Reset 1 - 99 Step 1 sec
100 - 250 Step 10 sec
15 sec
Check Hold Input Hold ? Hold No / Yes No
Maximum Cycle Enable
“Sync Set” must be “No” to view
this setting
MaxCycle ? MaxCycle No / Yes No
Maximum Cycle Time
“Max Cycle” must be “Yes” to
view this setting
Max Time Max Time 1 - 99 Step 1 sec
100 - 990 Step 10 sec
990 sec
Enable FollowBr ? Follow Bkr No / Yes No
Use of 52aInput 52a/Mancls 52a/ManCls 52a, Yes/Manual Close/No, Dis-
abled
No, Disabled
Number of Reclosures to Alarm
Enable
Cum. Recl? Cum. Recl No / Yes No
Number of Reclosures to Alarm
(Cum. Recl must Yes to view this
setting)
Cum. Recl #Cum. Recl 0 - 99 Step 1
100 - 990 Step 10
990 recl
Breaker Limit Operations:
- Breaker Operation Enable Br Oper. ? Bkr Oper No / Yes No
- Breaker Limit Number Max Count Limit Count 0 - 99 Step 1
100 - 250 Step 10
250 recl
- Breaker Limit Duration Duration Duration 1 - 99 Step 1 min
100 - 250 Step 10 min
250 min
-Breaker Recovery Time
“Br Oper.?” must be “Yes” to
view these settings
Recovery Recovery 1 - 99 Step 1 min
100 - 250 Step 10 min
1 min
Table 2-6: RECLOSING SETTINGS WITH RANGES (Sheet 3 of 4)
Setting
Function
Display
RCP
Display
Value
Displayed
Factory
Default
* Settings available only with synchronism check option and when Sync Set? = Yes