Test menu &KDSWHU
8QGHUVWDQGWKH+0,WUHH
 7HVWPHQX
Use this menu to enable easier secondary injection tests of the REx 5xx terminal. It is 
possible to block functions to prevent trip of circuit breakers and activation of alarm sig-
nals etc. to the control room during the testing activities.
The selectable modes, from the HMI, is the TestMode and ConfigMode.
TestMode:
• Setting the terminal in test mode operation
• Blocking of one or several protection and control functions (selectable) during test 
operation.
• Blocking of one or several event functions (selectable) during test operation.
• Setting the disturbance report and the disturbance summary to On or Off during test 
operation.
ConfigMode:
• Setting the terminal in configuration mode operation. This will automatically be 
done when down-loading a configuration from the CAP configuration tool. When 
the down-loading is completed, the terminal automatically enters the normal mode.