65
Find the reason of an internal failure &KDSWHU
9LHZWKHWHUPLQDOXQLWVWDWXV
MPM-modWarning = 
Warning
There is a problem 
with:
• the real time clock.
• the time synchroni-
zation.
Set the clock.
If the problem persists, contact your ABB 
representative for service.
ADC-module = OK No problem detected. None.
ADC-module = Fail The A/D conversion 
module has failed.
Contact your ABB representative for ser-
vice.
Slot04BIM1 = Fail
(Example data, see 
following section for 
details)
I/O module has failed. Check that the I/O module has been config-
ured and connected to the IOP1- block.
If the problem persists, contact your ABB 
representative for service.
RealTimeClock = OK No problem detected. None.
RealTimeClock = 
Warning
The real time clock has 
been reset.
Set the clock.
TimeSync = OK No problem detected. None.
TimeSync = Warning No time synchroniza-
tion.
Check the synchronization source for prob-
lems. 
If the problem persists, contact your ABB 
representative for service.
,QGLFDWHGUHVXOW 3RVVLEOHUHDVRQ 3URSRVHGDFWLRQ