For example, if there is a configuration to use IEC 61850 9–2 analog data, but no
data arrives on the access point, then the IED will use substituted data and most
protection functions will be blocked. This condition will be indicated with a sub-
menu under Hints, where details about this condition are shown. The Hint menu is
a way to assist the user in troubleshooting.
The Hint menu is currently only available in English. All the entries
are in English, regardless of which language is selected.
The supported list of hints are as follows:
Table 23: Hint menu
Headline Explanation
Incorrect setting of SyncLostMode There are two explanations possible:
SyncLostMode
is set to
Block
, no time source is
configured to achieve the required accuracy.
Unless a high accuracy time source is selected,
the function dependent on high time accuracy
will be blocked.
SyncLostMode
is set to
BlockOnLostUTC
, but
there is no UTC capable synch source (GPS,
IRIG-B) used. Unless a UTC capable time
source is selected, the function dependent on
high time accuracy will be blocked.
Sampled value substituted
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
Time diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
Frequency diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
Invalid phase angle reference
The selected
PhaseAngleRef
corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
Table continues on next page
1MRK 506 383-UEN A Section 12
Troubleshooting
Line distance protection REL650 2.2 IEC 187