EasyManua.ls Logo

ABB Relion 605 Series - Page 85

ABB Relion 605 Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MDU07212-YN Rev. D Section 6
Installation
REF601 / REJ601 / REM601 79
Application Manual
Table 33: Binary Output configuration, continue
Binary output
Signal to
activate output
BO1
BO2
BO3
BO4
BO5
BO6
3Ith > Alm
3Ith> Blkcl
I2/I1> Str
I2> Start
Trip : I> / 51
(x)
(x)
(x)
Trip : I>> / 50-1
(x)
(x)
(x)
Trip : I>>> / 50-2
(x)
(x)
(x)
Trip : Io> / 51N
(x)
(x)
(x)
Trip : Io> / 50N
(x)
(x)
(x)
3Ith > Trip
I2/I1> Trip
I2> Trip
BF Stage1
BF Stage2
BF RecTrip
O->I Close
O->I InPro
O->I FinalTr
O->I Blocked
Signal 1
Signal 2
Signal 3
CB Open Command
(x)
(x)
CB Close Command
(x)
TCS Fault
Unit Ready
(x)
Output behavior : - = Non inverted, “I” = Inverted
Remark : “(..)” = Default setting

Table of Contents

Related product manuals