1MDU07212-YN Rev. D Section 6
Installation
REF601 / REJ601 / REM601 75
Application Manual
6.9 Setting table
Table 30: Settings
Parameter
Actual
value
Default
value
Unit
Range
Resolution
3I> / 51
I>
01.50
In
0.1...2.5; infinite
0.001
t>
01.00
s
0.0464
0.010
I> Curve
DT
-
DT, IEC NI, IEC VI, IEC LI, IEC EI, RI,
ANSI NI, ANSI VI, ANSI MI, ANSI EI,
-
k
0.02 1.6
0.010
3I>> / 50-1
I>>
04.00
In
0.220; infinite (sensor variant)
0.225; infinite (CT variant)
0.001
t>>
00.30
s
0.0464
0.010
3I>>> / 50-2
I>>
10.00
In
0.220; infinite (sensor variant)
0.225; infinite (CT variant)
0.001
t>>
00.03
s
0.0364
0.010
I0> / 51N
I0>
00.05
In
Ext.: 0.01...2.0; infinite
Int.: 0.12.0; infinite
0.001
t0>
01.50
s
0.04...64
0.010
I0> Curve
DT
-
DT, IEC NI, IEC VI, IEC LI, IEC EI, RI,
ANSI NI, ANSI VI, ANSI MI, ANSI EI,
-
k0
0.02 1.6
0.010
I0>> / 50N
I0>>
04.00
In
Ext.: 0.0512.5; infinite
Int.: 0.512.5; infinite
0.001
t0>>
00.05
s
0.0464
0.010
3I2f> / 68
Inrush
threshold
0.50
In
0.2...25 (sensor variant)
0.220 (CT variant)
0.010
Ratio Setting
30%
%
30%...50%,
5%
I2> / 46
I2>
0.30
In
0.11.5
0.010
tI2>
1.00
s
0.1 300
0.100
block protn
0
0=No
1=Yes
I2/I1> / 46PD
I2/I1>
015%
In
10100%
0.010
tI2/I1>
00.10
s
0.1 64
0.100
block protn
0
0=No
1=Yes