Section 6 1MDU07212-YN Rev. D
Installation
76 REF601 / REJ601 / REM601
Application Manual
Table 30 Settings, continue
Parameter
Actual
value
Default
value
Unit
Range
Resolution
3Ith> / 49
ϑ0
080
%
0.0100%
1%
ϑpowerOFF
4
-
14
1
Ib
1.0
In
0.1 1.5
0.100
τ
045
min
1.0300
1.000
τs
045
min
1.0300
1.000
ϑalm
121
%
50200%,
1%
ϑtrip
144
%
50200%,
1%
ϑstartinhibit
105
%
50200%,
1%
3I/IoBF / 51BF/51NBF
Icbfp
01.1
In
0.22.0
0.100
Iocbfp
01.1
In
0.12.0
0.100
t Retrip
0.10
s
0.060.5
0.010
t Backup
0.12
s
0.060.5
0.010
O -> I / 79
AR start
mode
1
-
1 = Trip, 2 = Gen. start and trip
1
CB ready
1
-
1 = OCO, 2 = CO
1
Shot
3
-
04
1
Activate t
sec
0.15
0.100
Pulse tp
sec
0.220
0.100
Cycle t1
sec
0.2300
0.010
Cycle t2
sec
0.2300
0.010
Cycle t3
sec
0.2300
0.010
Cycle t4
sec
0.2300
0.010
Reclaim tr
sec
1300
1
Block tb
sec
1300
1